BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M374510
Premises: 572 MADISON AVENUE MANHATTAN BIN: 1035778     Block: 1292   Lot: 15
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 590 MADISON AV Census Tract:   112.02 Health Area:  4800
27TH & 37TH FLOORS Admin Area:   M - MANHATTAN Inspection Area:   L
NEW YORK, NY 10022 Community Board:   105
DOB Cross Street(s):   EAST 56 STREET,    EAST 57 STREET
Status:   I - AWAITING INSPECTION REQUEST
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/05/2015 6:10 PM
Application Entered:   11/05/2015 Job Start Date:   11/05/2015
Last Change:   06/20/2017 Job End Date:   03/30/2016
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   URIM SYLA       On     06/20/2017      
Field Disp:   J - JOB IN PROGRESS
Energize Recommendation:  
Objection Disposition:  Y - PARTLY REMOVED

License #: 010487 Licensee Name: CIRO LUPO
Firm: 001787 Firm Name: COMMERCIAL ELECT CONT INC
Firm Phone: 718-784-3500  Firm Address: 10-28 47TH AVENUE LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $195.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: 590 MADISON LLC
Authorized Representative:  JOSEPH GREISH
Relationship To Owner:   BUILDING REP.


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  2  1 SET #2; 1 SET #6
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  120/208
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
027    25  30    19  92             
037    20  28    12  55          30 
Buildings Total 45  58    31  147               30 
Total Units : 311 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 06/30/2016
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  27TH FLOOR SUITES; C&E 37TH FLOOR ROOMS; 3701 - 3711

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M374510
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/29/2016 06/30/2016 EDB V (75) (3)
INSPECTION COMMENTS: P
 
(2) 06/20/2017 06/20/2017 UMS J Y (35) (0)
INSPECTION COMMENTS: SEE REMAINING OBJECTIONS

OBJECTION FOR APPLICATION #: M374510
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 027) NO FIRE STOP IN EL. RM. 300.21
OPEN 06/29/2016 06/29/2016
 
002 (999) OTHER
(FLOOR: 027) PANEL : MULTIWIRE CKT. NO GROUPED NO SIMULT. TRIP
OPEN 06/29/2016 06/29/2016
 
003 ( 45) FIXTURE NOT INSTALLED IN AN APPROVED MANNER
(ALL FLOORS) CEILING LIGHT NOT SECURED 410.30,36
RSLV 06/29/2016 06/29/2016 06/20/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order