| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 7) |
EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT) (GROUND FLOOR) EMT NEEDS SUPPORT |
RSLV |
01/28/2016 |
01/28/2016 |
05/25/2016 |
| |
| 002 |
(999) |
OTHER (GROUND FLOOR) BOXS NOT FLUSH WITH WOOD 314.20 |
RSLV |
01/28/2016 |
01/28/2016 |
05/25/2016 |
| |
| 003 |
(999) |
OTHER (GROUND FLOOR) BOXS NOT BONDED M.C 250.148 |
RSLV |
01/28/2016 |
01/28/2016 |
05/25/2016 |
| |
| 004 |
(999) |
OTHER (GROUND FLOOR) OUTLET BOXS NOT COVERED 314.25 |
RSLV |
01/28/2016 |
01/28/2016 |
05/25/2016 |
| |
| 005 |
(999) |
OTHER (GROUND FLOOR) NO GFI WITHIN 6 FT OF SINK 210.8 |
RSLV |
01/28/2016 |
01/28/2016 |
05/25/2016 |
| |
| 006 |
(999) |
OTHER (GROUND FLOOR) BOX NOT SUPPORTED IN CEILING 314.23 |
RSLV |
01/28/2016 |
01/28/2016 |
05/25/2016 |
| |
| 007 |
(999) |
OTHER (GROUND FLOOR) KO SEALS MISSING ON CEILING BOX. 110.12 |
RSLV |
01/28/2016 |
01/28/2016 |
05/25/2016 |