BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M374393
Premises: 43 EAST 34 STREET MANHATTAN BIN: 1017114     Block: 864   Lot: 7501
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 199 MADISON AV Census Tract:   74 Health Area:  5200
GROUND FLOOR Admin Area:   M - MANHATTAN Inspection Area:   P
NEW YORK, NY 10016 Community Board:   106
DOB Cross Street(s):   EAST 34 STREET,    EAST 35 STREET
Status:   C - JOB IS SIGNED OFF 05/25/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/03/2015 6:27 PM
Application Entered:   11/03/2015 Job Start Date:   11/09/2015
Last Change:   05/25/2016 Job End Date:   12/30/2015
Appointment Status:   
Last Inspection By:   PANAYOTEDIS, STEPHEN       On     05/25/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011528 Licensee Name: CARLO A BERARDI
Firm: 003006 Firm Name: BERARDI ELEC'L CONTR'G IN
Firm Phone: 718-460-8607  Firm Address: 36-07 169TH STREET FLUSHING NY 11358 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $49.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   RETAIL
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: MANUFACTURE MICHEL CLUISE
Authorized Representative:  BEN KOBI
Relationship To Owner:   AGENT


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND    20  21                 
Buildings Total 20  21                    
Total Units : 47 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 01/29/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M374393
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/28/2016 01/29/2016 STP V (40) (7)
INSPECTION COMMENTS: PANEL EXISTING
 
(2) 03/28/2016 03/29/2016 CBK N (30) (0) Y
INSPECTION COMMENTS: CONTRACTOR DIDN'T SHOW.
 
(3) 04/18/2016 04/19/2016 NRS N (31) (0) Y
INSPECTION COMMENTS: CONTRACTOR NO SHOW.
 
(4) 05/05/2016 05/05/2016 NRS N (38) (0) Y
INSPECTION COMMENTS: CONTRACTOR NO SHOW.
 
(5) 05/25/2016 05/25/2016 STP C R (30) (0)
INSPECTION COMMENTS: PASS. VIOLATIONS REMOVED.

OBJECTION FOR APPLICATION #: M374393
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
(GROUND FLOOR) EMT NEEDS SUPPORT
RSLV 01/28/2016 01/28/2016 05/25/2016
 
002 (999) OTHER
(GROUND FLOOR) BOXS NOT FLUSH WITH WOOD 314.20
RSLV 01/28/2016 01/28/2016 05/25/2016
 
003 (999) OTHER
(GROUND FLOOR) BOXS NOT BONDED M.C 250.148
RSLV 01/28/2016 01/28/2016 05/25/2016
 
004 (999) OTHER
(GROUND FLOOR) OUTLET BOXS NOT COVERED 314.25
RSLV 01/28/2016 01/28/2016 05/25/2016
 
005 (999) OTHER
(GROUND FLOOR) NO GFI WITHIN 6 FT OF SINK 210.8
RSLV 01/28/2016 01/28/2016 05/25/2016
 
006 (999) OTHER
(GROUND FLOOR) BOX NOT SUPPORTED IN CEILING 314.23
RSLV 01/28/2016 01/28/2016 05/25/2016
 
007 (999) OTHER
(GROUND FLOOR) KO SEALS MISSING ON CEILING BOX. 110.12
RSLV 01/28/2016 01/28/2016 05/25/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back