| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
1 |
SET 3#2AWG |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER NO TR RECEPTACLE PROVIDED T-OUT 406.11 |
OPEN |
12/03/2015 |
12/03/2015 |
|
| |
| 002 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED PANEL: ARC FAULT BREAKERS NEEDED IN PANEL 210.12B |
OPEN |
12/03/2015 |
12/03/2015 |
|
| |
| 003 |
(999) |
OTHER CLOSET: CLOSET LIGHT CLOSE RO STORAGE SPACE 410.16C |
OPEN |
12/03/2015 |
12/03/2015 |
|
| |
| 004 |
(999) |
OTHER WOOD PANELLING: RECEPTACLE BOX SET BACK IN COMBUSTIBLE MATERICALS T-OUT WOOD PANELING 314.20 |
OPEN |
12/03/2015 |
12/03/2015 |
|
| |
| 005 |
(999) |
OTHER BATHRM: NO RECEPTACLE PROVIDED BY SINK 210.52D |
OPEN |
12/03/2015 |
12/03/2015 |
|
| |
| 006 |
(999) |
OTHER (FLOOR: 004)BATHROOM LIGHT FIXTURES ARE LOCATED WITHIN THE SHOWER WET ZONE(410.10D) |
RSLV |
02/17/2016 |
02/17/2016 |
03/16/2016 |
| |
| 007 |
(999) |
OTHER (FLOOR: 004) RECEPTACLE IN ENTRY WAY MUST BE TR TYPE (406.11) |
RSLV |
02/17/2016 |
02/17/2016 |
03/16/2016 |
| |
| 008 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (FLOOR: 004) NO GFCI PROTECTION ON KITCHEN COUNTER 210.8 |
OPEN |
03/22/2017 |
03/22/2017 |
|
| |
| 009 |
(999) |
OTHER (FLOOR: 004) IMPROPER BATH RM OUTLET PLACEMENT 210.52 |
OPEN |
03/22/2017 |
03/22/2017 |
|
| |
| 010 |
(999) |
OTHER (FLOOR: 004) NO OUTLET PROVIDED FOR KITCHEN PENINSULA 210.52 |
OPEN |
03/22/2017 |
03/22/2017 |
|
| |
| 011 |
(999) |
OTHER (FLOOR: 004) MEDICINE CAB RECEPTACLE FACE UP 406.4 E |
OPEN |
09/15/2016 |
09/15/2016 |
|