| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
1 |
1- 100 AMPS SS 3-PH |
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
1 |
1-SET OF 4 #2 |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
1 |
1-100 AMPS 3-PH |
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 7) |
EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT) (ALL FLOORS) BSMT: E.M.T.IS NOT PROPERLY SUPPORTED (BSMT)(E.M.T.FROM TROUGH) |
RSLV |
11/12/2015 |
11/12/2015 |
08/29/2019 |
| |
| 002 |
(999) |
OTHER (ALL FLOORS) BSMT: INSUFFICIENT WORK SPACE NOT PROVIDED.. 110.26BSMT (DISCONNECT & METER PAN) NO CLEARANCE |
RSLV |
11/12/2015 |
11/12/2015 |
08/29/2019 |
| |
| 003 |
(999) |
OTHER (FLOOR: 001) FLOOR 1 430.30 NOT ACCESS TO INSPECT ELECTRICAL PANEL. |
RSLV |
08/29/2019 |
08/29/2019 |
09/03/2019 |
| |
| 004 |
(999) |
OTHER (FLOOR: 001) FLOOR 1 NOT ACCESS TO INSPECT DEVICES ON FIRST FLOOR. |
RSLV |
08/29/2019 |
08/29/2019 |
09/03/2019 |
| |
| 005 |
(999) |
OTHER (BASEMENT) BSMT 250.52 NOT ACCESS TO INSPECT WATER MAIN. |
RSLV |
08/29/2019 |
08/29/2019 |
09/03/2019 |
| |
| 006 |
(999) |
OTHER (GROUND FLOOR)GND. 406.4 HVAC RECEPTACLE ARE NOT WATER RESISTANCE LISTED |
OPEN |
08/29/2019 |
08/29/2019 |
|
| |
| 007 |
(999) |
OTHER (GROUND FLOOR) GND 250.122 EGC IN USE NOT PER CODE ( HVAC UNIT ) |
OPEN |
08/29/2019 |
08/29/2019 |
|
| |
| 008 |
(999) |
OTHER (FLOOR: 001)COVER PLATE ON COUNTER BY SINK NOT LISTED FOR USE ( MULBERRY NEEDED) , ART. 110 |
RSLV |
09/03/2019 |
09/03/2019 |
|
| |
| 009 |
(999) |
OTHER (FLOOR: 001) CONNECTION AT DRYER , NO CONNECTOR , ART. 110 |
RSLV |
09/03/2019 |
09/03/2019 |
|
| |
| 010 |
(999) |
OTHER (BASEMENT)MUST FILE NEW APP TO AMEND APP , NO SERVICE SWITCH WAS INSTALLED |
OPEN |
09/03/2019 |
09/03/2019 |
|