Electrical Application Details for App #: M374120
Premises: 2 WEST 13 STREET MANHATTAN BIN: 1009617     Block: 576   Lot: 36
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 2 W 13 ST Census Tract:   63
CELLAR THROUGH ROOF Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10011 Community Board:   102
Special Place Name:   THE NEW SCHOOL
DOB Cross Street(s):    5 AVENUE,    AVENUE OF THE AMERICAS
Status:   C - JOB IS SIGNED OFF 02/13/2017
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   10/27/2015 Job Start Date:   10/21/2015
Last Change:   02/13/2017 Job End Date:   03/20/2016
Appointment Status:   
Last Inspection By:   RACEWICZ, TOMASZ       On     01/19/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011626 Licensee Name: ROCCO PROGANO III
Firm: 004173 Firm Name: WISE ELECTRICAL SVCS INC
Firm Phone: 212-481-3200  Firm Address: 63-15 METROPOLITAN AVENUE MIDDLE VILLAGE NY 11379 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $503.50
Hurricane Sandy Damage:   No
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   W - School
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   53231     Submittal #: 15A0590  
Owner / Occup: LIA GARTNER
Owner Business Name: THE NEW SCHOOL
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  2  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  1  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL                500 
013        10  176  12     
Buildings Total   10     177     12     500 
Total Units : 704 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 08/04/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  CHILLER PLANT

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M374120
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/03/2016 08/04/2016 EDB V (105) (7)
INSPECTION COMMENTS: SEE ATTACHMENT
 
(2) 10/14/2016 10/17/2016 EDB J Y (90) (0)
INSPECTION COMMENTS: CONTRACTOR NEED TO FIX THE DRAWING.
 
(3) 01/19/2017 01/19/2017 TOR C R (80) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: M374120
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 42) BUSHINGS ARE MISSING OR LOOSE
(ALL FLOORS) PULL BOX : 600 MCM
RSLV 08/03/2016 08/03/2016 10/14/2016
 
002 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(ALL FLOORS) T-OUT : PULL BOX(S) TOO SMALL 314.28
RSLV 08/03/2016 08/03/2016 10/14/2016
 
003 (999) OTHER
(ALL FLOORS) NO ARC FLASH WARNING ON NEW EQUIPMENT 110.16
RSLV 08/03/2016 08/03/2016 10/14/2016
 
004 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(CELLAR) INSTALLATION NOT PER DRAWING
RSLV 08/03/2016 08/03/2016 01/19/2017
 
005 (261) ELECTRICAL CLOSETS/SERVICE ROOM IS USED FOR OTHER PURPOSES
(CELLAR) EL. RM. USED FOR STORAGE
RSLV 08/03/2016 08/03/2016 10/14/2016
 
006 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(CELLAR) SEC. SW. ( T-FMR ) NOT OPEN ON 90 DEGREE 110.26
RSLV 08/03/2016 08/03/2016 10/14/2016
 
007 (999) OTHER
(CELLAR) NO PANIC BAR ON THE EXIT DOOR 110.26
RSLV 08/03/2016 08/03/2016 10/14/2016