| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
1 |
1-100A |
| C. 201 Up to 600 AMPS |
1 |
1-400A |
| D. 601 Up to 1200 AMPS |
3 |
2-800A,1-1200A |
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
6 |
6-500K CMIL |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER (ALL FLOORS)CELLAR: NEUTRAL BONDED BEFORE FIRST DISCONNECT RT-1 RT-2.. 250.24 |
RSLV |
10/26/2015 |
10/26/2015 |
11/16/2017 |
| |
| 002 |
(999) |
OTHER (ALL FLOORS)SERVICE ROOM: DOUBLE LUG GROUND UNLIKE METAL(CU-AL).. 110.12 |
RSLV |
10/26/2015 |
10/26/2015 |
11/16/2017 |
| |
| 003 |
(999) |
OTHER (ALL FLOORS) SERVICE ROOM: GROUNDS RUN UNWORKMAN LIKE.. 110.14 |
RSLV |
10/26/2015 |
10/26/2015 |
11/16/2017 |
| |
| 004 |
(999) |
OTHER (ALL FLOORS)CELLAR: MULTIWIRE CIRCUITS NEED SIMULTANEOUS TRIP.. 210.4 |
RSLV |
10/26/2015 |
10/26/2015 |
11/16/2017 |
| |
| 005 |
(999) |
OTHER (ALL FLOORS)OUTSIDE SERVICE: EMT NOT SUPPORTED OUTSIDE SERVICE ROOM.. 358.30 |
RSLV |
10/26/2015 |
10/26/2015 |
11/16/2017 |
| |
| 006 |
(999) |
OTHER (ALL FLOORS) SERVICE RM: SECONDARY GEC NOT PROVIDED.. 250.53 |
RSLV |
10/26/2015 |
10/26/2015 |
11/16/2017 |
| |
| 007 |
(999) |
OTHER (ALL FLOORS) ROOF: NO G.F.I. W/I 25' FOR A/C UNITS.. 210.8 |
RSLV |
10/26/2015 |
10/26/2015 |
02/10/2017 |
| |
| 008 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (ALL FLOORS) ROOF: THE GENERATOR MODEL NUMBER AND SIZE |
RSLV |
10/26/2015 |
10/26/2015 |
12/12/2017 |
| |
| 009 |
(999) |
OTHER (ALL FLOORS) ROOF: GENERATOR NOT LABELED FOR USE IN U.S.A.. 110.2 |
RSLV |
10/26/2015 |
10/26/2015 |
12/12/2017 |
| |
| 010 |
(999) |
OTHER (ALL FLOORS)GENERATOR LABEL APPEARS TO BE MOVED/NOT ORIGINAL.. 110.2 |
RSLV |
10/26/2015 |
10/26/2015 |
12/12/2017 |
| |
| 011 |
(999) |
OTHER (ALL FLOORS) ROOF: CONTRACTOR MUST PROVE GENERATOR TESTED.. 700.4 |
RSLV |
10/26/2015 |
10/26/2015 |
11/16/2017 |
| |
| 012 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED (CELLAR) FROM CEL. TO SUB. : WIRING TO F/P NOT PER AM. 695.6 |
RSLV |
02/10/2017 |
02/10/2017 |
11/16/2017 |
| |
| 013 |
(999) |
OTHER (CELLAR) EL. RM. : NO PANIC BAR PROVIDED ON THE DOOR 110.26 |
RSLV |
02/10/2017 |
02/10/2017 |
11/16/2017 |
| |
| 014 |
( 14) |
CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE (SUB-CELLAR) F/P S. SW. UNDERSIZE AM. 695.4 |
RSLV |
02/10/2017 |
02/10/2017 |
11/16/2017 |