Electrical Application Details for App #: M373917
Premises: 87 CHAMBERS STREET MANHATTAN BIN: 1089729     Block: 149   Lot: 7503
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 87 CHAMBERS ST Census Tract:   21
CELLAR Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10007 Community Board:   101
Related Job Number:    120571194
DOB Cross Street(s):   BROADWAY,    CHURCH STREET
Status:   C - JOB IS SIGNED OFF 04/05/2018
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   10/21/2015 Job Start Date:   10/15/2015
Last Change:   04/05/2018 Job End Date:   12/30/2016
Appointment Status:   
Last Inspection By:   CONROY BLAKE       On     12/12/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 012245 Licensee Name: PETER ARANA
Firm: 003988 Firm Name: SANT-TEC ELECTRIC INC
Firm Phone: 718-644-7645  Firm Address: 516 INDUSTRIAL LOOP 2ND FL STATEN ISLAND NY 10309 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $1,300.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   52990     Submittal #: 15A0233  
Owner / Occup: YEHUDA MOR
Owner Business Name: IBC CHAMBERS, LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  1-100A
C. 201 Up to 600 AMPS  1  1-400A
D. 601 Up to 1200 AMPS  3  2-800A,1-1200A
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  6  6-500K CMIL
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 18 #4-Wire 1 #10-Wire 2
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 10/21/2015 Notice: 1 - FIRST NOTICE 02/13/2017
Power Issued: 10/21/2015 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  ELECTRICAL SERVICE

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M373917
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/26/2015 11/02/2015 ECH A E (60) (11) Y
INSPECTION COMMENTS: SEE PERMIT #M348369
 
(2) 02/10/2017 02/13/2017 EDB V Y (75) (3)
INSPECTION COMMENTS: NO ADVISORY BOARD DRAWING AT INSPECTION. SEE ATTACHMENT. RESTRICTED ACCESS TO ROOF ( SNOW CONDITION ).
 
(3) 11/16/2017 11/17/2017 CBK J Y (105) (0)
INSPECTION COMMENTS: OBJECTION PARTIALLY REMOVED.
 
(4) 12/12/2017 12/12/2017 CBK C R (58) (0)
INSPECTION COMMENTS: OBJECTION RESOLVED.

OBJECTION FOR APPLICATION #: M373917
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS)CELLAR: NEUTRAL BONDED BEFORE FIRST DISCONNECT RT-1 RT-2.. 250.24
RSLV 10/26/2015 10/26/2015 11/16/2017
 
002 (999) OTHER
(ALL FLOORS)SERVICE ROOM: DOUBLE LUG GROUND UNLIKE METAL(CU-AL).. 110.12
RSLV 10/26/2015 10/26/2015 11/16/2017
 
003 (999) OTHER
(ALL FLOORS) SERVICE ROOM: GROUNDS RUN UNWORKMAN LIKE.. 110.14
RSLV 10/26/2015 10/26/2015 11/16/2017
 
004 (999) OTHER
(ALL FLOORS)CELLAR: MULTIWIRE CIRCUITS NEED SIMULTANEOUS TRIP.. 210.4
RSLV 10/26/2015 10/26/2015 11/16/2017
 
005 (999) OTHER
(ALL FLOORS)OUTSIDE SERVICE: EMT NOT SUPPORTED OUTSIDE SERVICE ROOM.. 358.30
RSLV 10/26/2015 10/26/2015 11/16/2017
 
006 (999) OTHER
(ALL FLOORS) SERVICE RM: SECONDARY GEC NOT PROVIDED.. 250.53
RSLV 10/26/2015 10/26/2015 11/16/2017
 
007 (999) OTHER
(ALL FLOORS) ROOF: NO G.F.I. W/I 25' FOR A/C UNITS.. 210.8
RSLV 10/26/2015 10/26/2015 02/10/2017
 
008 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(ALL FLOORS) ROOF: THE GENERATOR MODEL NUMBER AND SIZE
RSLV 10/26/2015 10/26/2015 12/12/2017
 
009 (999) OTHER
(ALL FLOORS) ROOF: GENERATOR NOT LABELED FOR USE IN U.S.A.. 110.2
RSLV 10/26/2015 10/26/2015 12/12/2017
 
010 (999) OTHER
(ALL FLOORS)GENERATOR LABEL APPEARS TO BE MOVED/NOT ORIGINAL.. 110.2
RSLV 10/26/2015 10/26/2015 12/12/2017
 
011 (999) OTHER
(ALL FLOORS) ROOF: CONTRACTOR MUST PROVE GENERATOR TESTED.. 700.4
RSLV 10/26/2015 10/26/2015 11/16/2017
 
012 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(CELLAR) FROM CEL. TO SUB. : WIRING TO F/P NOT PER AM. 695.6
RSLV 02/10/2017 02/10/2017 11/16/2017
 
013 (999) OTHER
(CELLAR) EL. RM. : NO PANIC BAR PROVIDED ON THE DOOR 110.26
RSLV 02/10/2017 02/10/2017 11/16/2017
 
014 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(SUB-CELLAR) F/P S. SW. UNDERSIZE AM. 695.4
RSLV 02/10/2017 02/10/2017 11/16/2017