BIS Menu  |  Property Permits  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M373887
Premises: 39 EAST 85 STREET MANHATTAN BIN: 1046831     Block: 1497   Lot: 21
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 1153 MADISON AV Census Tract:   150.01 Health Area:  3600
GRD FLOOR Admin Area:   M - MANHATTAN Inspection Area:   J
NEW YORK, NY 10028 Community Board:   108
DOB Cross Street(s):   EAST 85 STREET,    EAST 86 STREET
Status:   C - JOB IS SIGNED OFF 06/15/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/21/2015 10:00 AM
Application Entered:   10/21/2015 Job Start Date:   10/21/2015
Last Change:   06/15/2016 Job End Date:   04/20/2016
Appointment Status:   
Last Inspection By:   RAMJAG, BUDRAM       On     06/14/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011463 Licensee Name: EMANUEL M KONTOROUHAS
Firm: 003436 Firm Name: CITYWIDE ELEC'L WIRING IN
Firm Phone: 718-433-9115  Firm Address: 20-22 STEINWAY STREET ASTORIA NY 11105 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $230.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   RETAIL
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: THOMAS CARCHIETTA
Owner Business Name: WESTMINSTER HOUSE OWNERS
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  2  100 AMP
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  100 AMP
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 2 #10-Wire 1
Existing Meters 8 + New Meters 3 - Removed Meters 1 = Total Meters 10

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 10/21/2015 Notice: C - CALL TO OFFICE 05/04/2016
Power Issued: 10/21/2015 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M373887
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/15/2016 03/15/2016 GYM V (50) (1)
INSPECTION COMMENTS: PROVIDED FUSE COORDINATION.
 
(2) 04/22/2016 05/04/2016 CBK J X (45) (0) Y
INSPECTION COMMENTS: PROOF OF COORDINATION REQUIRED.
 
(3) 06/14/2016 06/15/2016 BUR C R (40) (0)
INSPECTION COMMENTS: OBJECTION RESOLVED

OBJECTION FOR APPLICATION #: M373887
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(BASEMENT)FUSE COORDINATION REQUIRED ART 240.12 (EXISTING 800 AMP SER. SW. NEW100 AMP DISC. SW' AUY 800 AMP FUSE TO BREAKER)
RSLV 03/15/2016 03/15/2016 06/14/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Property Permits  |  Electrical Inspection Work Order  |  Back