BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M373875
Premises: 1614 3 AVENUE MANHATTAN BIN: 1048267     Block: 1519   Lot: 40
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 1614 3 AV Census Tract:   148.02 Health Area:  3600
GROUND FLOOR SALES OFFICE Admin Area:   M - MANHATTAN Inspection Area:   J
NEW YORK, NY 10128 Community Board:   108
Special Place Name:   GROUND FLOOR
DOB Cross Street(s):   EAST 90 STREET,    EAST 91 STREET
Status:   P - OBJECTN PENDING AT CONTRACTOR 01/14/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/21/2015 4:52 AM
Application Entered:   10/21/2015 Job Start Date:   10/22/2015
Last Change:   01/19/2016 Job End Date:   12/31/2015
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   GANITIS, PHILLIP       On     01/13/2016      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 012691 Licensee Name: JOHN P DOHENY
Firm: 004376 Firm Name: S.E. ELECTL CONTNG CORP
Firm Phone: 718-986-7554  Firm Address: 25 EAST 233RD STREET BRONX NY 10470 

Historical Licensees and Firms:
License # Licensee Name Firm # Firm Name  
009225 PASTUSAK, WALTER 004376 S.E. ELECTL CONTNG CORP

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $113.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ELY SAMUELS
Owner Business Name: EL-KAM REALTY
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  1-24 CKT-1 PH PANEL
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND    27  20    30         
Buildings Total 27  20    30              
Total Units : 93 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 01/14/2016
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M373875
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/16/2015 12/17/2015 TOR N (20) (0) Y
INSPECTION COMMENTS: CALLED CONTRACTOR --- CONTRACTOR NO SHOW
 
(2) 01/13/2016 01/14/2016 PHG V (45) (3)
INSPECTION COMMENTS: ALL OBJECTIONS IN BSMT

OBJECTION FOR APPLICATION #: M373875
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(BASEMENT) NO GRND IN FMC CHANGE OVER IN BSMT 250.118
OPEN 01/13/2016 01/13/2016
 
002 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
(BASEMENT) EMT NOT SUPPORTED IN BSMT
OPEN 01/13/2016 01/13/2016
 
003 (999) OTHER
(BASEMENT) BROKEN FMC IN BSMT 250.4
OPEN 01/13/2016 01/13/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.