BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M373746
Premises: 236 WEST 26 STREET MANHATTAN BIN: 1014205     Block: 775   Lot: 60
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 236 W 26 ST Census Tract:   91 Health Area:  5200
1 FLOOR REAR LOBBY Admin Area:   M - MANHATTAN Inspection Area:   P
NEW YORK, NY 10001 Community Board:   104
Special Place Name:   C. IANNACONE
Related Job Number:    121124513
DOB Cross Street(s):    7 AVENUE,    8 AVENUE
Status:   C - JOB IS SIGNED OFF 08/08/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/18/2015 11:50 AM
Application Entered:   10/18/2015 Job Start Date:   10/18/2015
Last Change:   08/08/2017 Job End Date:   01/20/2016
Appointment Status:   
Last Inspection By:   CONROY BLAKE       On     08/08/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010100 Licensee Name: FERDINAND IANNACONE
Firm: 000883 Firm Name: LITE-TRON ELEC'L CORP.
Firm Phone: 212-741-6326  Firm Address: 236 WEST 26TH STREET NEW YORK NY 10001 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $117.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: CHRISTINE IANNACONE
Authorized Representative:  FRED IANNACONE
Relationship To Owner:   HUSBAND


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  100 AMP 30 CIRCUIT
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001  REAR  30  27  11  20  30     
Buildings Total 30  27  11  20  30            
Total Units : 120 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 06/15/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  EXISTING SERVICE AND SUB FEEDER NEW PANEL AND BRANCH WIRING

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M373746
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/15/2017 06/15/2017 PHG V (30) (5)
INSPECTION COMMENTS: CONTRACTOR TO FIX APP TO REFLECT WORK
 
(2) 08/08/2017 08/08/2017 CBK C R (40) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED.

OBJECTION FOR APPLICATION #: M373746
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (340) RECEPTACLES NOT TAMPERPROOF
(GROUND FLOOR) NO TAMPER OUTLETS T OUT 406.11
RSLV 06/15/2017 06/15/2017 08/08/2017
 
002 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(GROUND FLOOR) GROUND WIRE USED AS PHASE CONDUCTOR IN PANEL 250.118
RSLV 06/15/2017 06/15/2017 08/08/2017
 
003 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(GROUND FLOOR) AFCI NEEDED T OUT 210.12
RSLV 06/15/2017 06/15/2017 08/08/2017
 
004 (999) OTHER
(GROUND FLOOR) NO WATER PROOF TRIM LIGHT IN SHOWER 410.10
RSLV 06/15/2017 06/15/2017 08/08/2017
 
005 (999) OTHER
(GROUND FLOOR) NO HANDLE TIES FOR MULTI WIRE CKT 210.4
RSLV 06/15/2017 06/15/2017 08/08/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.