Electrical Application Details for App #: M373724
Premises: 229 WEST 28 STREET MANHATTAN BIN: 1014255     Block: 778   Lot: 20
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 229 W 28 ST Census Tract:   95 Health Area:  5200
9TH FLOOR Admin Area:   M - MANHATTAN Inspection Area:   P
NEW YORK, NY 10001 Community Board:   105
DOB Cross Street(s):    7 AVENUE,    8 AVENUE
Status:   C - JOB IS SIGNED OFF 12/20/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  10/16/2015 1:15 PM
Application Entered:   10/16/2015 Job Start Date:   10/19/2015
Last Change:   12/20/2016 Job End Date:   10/19/2015
Appointment Status:   
Last Inspection By:   SCHULER, THOMAS       On     10/11/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012656 Licensee Name: PAUL COLLETTA
Firm: 004494 Firm Name: PCS ELECTRICAL SVCS INC
Firm Phone: 646-522-3514  Firm Address: 43-01 21ST STREET, SUITE 122-B LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $145.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: N/A N/A
Owner Business Name: NOOM
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  200 AMPS
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
009    95  120  12               
Buildings Total 95  120  12                  
Total Units : 231 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 09/12/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M373724
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/09/2016 09/12/2016 EDB V (55) (7)
INSPECTION COMMENTS: SEE ATTACHMENT.
 
(2) 10/11/2016 10/12/2016 TUR C R (30) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED

OBJECTION FOR APPLICATION #: M373724
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 10) BRANCH CIRCUIT CONDUCTORS ARE NOT PROPER SIZE
(FLOOR: 009) OVER FUSE A/C UNIT
RSLV 09/09/2016 09/09/2016 10/11/2016
 
002 ( 24) ARMORED CABLES ARE NOT PROPERLY SECURED
(FLOOR: 009) EL. CLOSET : AC CABLE NOT PROPERLY SECURED
RSLV 09/09/2016 09/09/2016 10/11/2016
 
003 ( 30) OUTLET BOXES ARE NOT SECURED
(FLOOR: 009) EL. CLOSET : SELLING SPLICE BOX NOT SECURED
RSLV 09/09/2016 09/09/2016 10/11/2016
 
004 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
(FLOOR: 009) PANEL AND A/C DISC. SW.
RSLV 09/09/2016 09/09/2016 10/11/2016
 
005 ( 36) CONDUCTORS ARE NOT PROPERLY COLOR CODED
(FLOOR: 009) A/C DISC. SW.
RSLV 09/09/2016 09/09/2016 10/11/2016
 
006 ( 45) FIXTURE NOT INSTALLED IN AN APPROVED MANNER
(FLOOR: 009)SELLING LIGHT FIXTURE NOT PROPERLY SECURED 410.30,36
RSLV 09/09/2016 09/09/2016 10/11/2016
 
007 ( 53) GFCI HAS NOT BEEN PROVIDED
(FLOOR: 009) WATER FOUNTAIN MISSING GFCI 422.52
RSLV 09/09/2016 09/09/2016 10/11/2016