| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 19) |
DEFECTIVE WIRING IS IN USE (FLOOR: 002) EXISTING MULTIWIRE CIR?UIT TERMINATEDON A TWIN BREAKER |
RSLV |
04/25/2016 |
04/25/2016 |
01/26/2017 |
| |
| 002 |
( 19) |
DEFECTIVE WIRING IS IN USE (FLOOR: 002) 208V A/C 'WHITE' PHASE CONDUCTOR USED AS NEUTRAL PATH FOR BEDROOMRECEPTACLES |
RSLV |
04/25/2016 |
04/25/2016 |
11/28/2016 |
| |
| 003 |
( 19) |
DEFECTIVE WIRING IS IN USE (FLOOR: 002) BEDROOM RECES. REVERSE WIRED |
RSLV |
04/25/2016 |
04/25/2016 |
11/28/2016 |
| |
| 004 |
(211) |
RECEPTACLE IS NOT PROPERLY BONDED/GROUNDED (FLOOR: 002) NOT AS PER 250.8 |
RSLV |
04/25/2016 |
04/25/2016 |
01/26/2017 |
| |
| 005 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED (FLOOR: 002) PANEL: NO CONDUIT, NO E.G.C. USED |
RSLV |
04/25/2016 |
04/25/2016 |
11/28/2016 |
| |
| 006 |
(356) |
RACEWAY LACKS MECHANICAL CONTINUITY (FLOOR: 002)#8AWG FEEDERS ENTER PANEL THROUGH A NIPPLE, NO CONDUIT IN WALL |
RSLV |
04/25/2016 |
04/25/2016 |
11/28/2016 |
| |
| 007 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED (FLOOR: 002) NON COMBINATION TYPE INSTALLED |
RSLV |
04/25/2016 |
04/25/2016 |
11/28/2016 |
| |
| 008 |
(999) |
OTHER (FLOOR: 002) NO SIMULTANEOUS TRIP PROVIDED 314.20 |
RSLV |
04/25/2016 |
04/25/2016 |
01/26/2017 |
| |
| 009 |
(999) |
OTHER (FLOOR: 002) PPANEL MAIN BREAKER NOT AS PER 408.36(D) |
RSLV |
04/25/2016 |
04/25/2016 |
01/26/2017 |
| |
| 010 |
(331) |
DEVICE REMOVAL INTERRUPTS CIRCUIT CONTINUITY (FLOOR: 003) RECEPTACLES WITH MULTIWIRES |
RSLV |
04/25/2016 |
04/25/2016 |
01/26/2017 |
| |
| 011 |
( 58) |
FIXTURE NOT PROPERLY LOCATED IN CLOTHES CLOSET (FLOOR: 003) CLOSET LIGHTS |
RSLV |
04/25/2016 |
04/25/2016 |
11/28/2016 |
| |
| 012 |
(999) |
OTHER (FLOOR: 002)INSUFFICIENT BOX SPACE FOR NEW WALL DEVICES 110.3B, 314.16 |
RSLV |
11/28/2016 |
11/28/2016 |
01/26/2017 |