Electrical Application Details for App #: M373082
Premises: 212 BROADWAY MANHATTAN BIN: 1001245     Block: 89   Lot: 12
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 222 BROADWAY Census Tract:   15.01
CELL,1,2 Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10038 Community Board:   101
Special Place Name:   ZARA
DOB Cross Street(s):   FULTON STREET,    ANN STREET
Status:   C - JOB IS SIGNED OFF 03/30/2018
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   10/01/2015 Job Start Date:   10/01/2015
Last Change:   03/30/2018 Job End Date:   10/01/2015
Appointment Status:   
Last Inspection By:   RACEWICZ, TOMASZ       On     03/29/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011722 Licensee Name: FRANK ARAGONA
Firm: 003309 Firm Name: EMANON ELECTRIC INC.
Firm Phone: 718-848-2891  Firm Address: 237 WEST 35TH STREET SUITE503 NEW YORK NY 10001 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $2,450.75
Hurricane Sandy Damage:   No
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   RETAIL CLOTHING
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   53124     Submittal #: 15A0453  
Owner / Occup: BRIAN TUBMAN
Owner Business Name: SCHIMENTI CONSTRUCTION
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  1  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  2  
D. Over 250 MCM  4  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  5  
D. 3 Phase Over 225 AMPS  2  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  1  
B. Each Additional 10 Floors Or Less  4  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    326  87    21  326  32  90  79 
001    568  98    27  568  19  40     
002    622  35    15  622  10  225 
Buildings Total 1516  220    63  1516     140        304 
Total Units : 3765 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 02/08/2018
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  WIRING FOR ELEVATOR/ESCALATOR

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M373082
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/30/2015 11/09/2015 TOR A (210) (13) Y
INSPECTION COMMENTS: DID NOT INSPECT ELEVATORS OR MAIN SERVICE.ADVISORY BOARD DRAWINGS NO MATCH.ONLY INSPECTED BRANCH PANELS NOT MDP & TRANSFORMER
 
(2) 01/06/2016 01/07/2016 EDB V Y (100) (2)
INSPECTION COMMENTS: NO ADVISORY BOARD DRAWING AT INSPECTION.
 
(3) 09/21/2016 09/22/2016 CBK J Y (180) (0)
INSPECTION COMMENTS: OBJECTIONS PARTIALLY REMOVED.
 
(4) 01/23/2017 01/24/2017 CBK J X (75) (0) Y
INSPECTION COMMENTS: NOT REMOVED.
 
(5) 08/09/2017 08/09/2017 MQY N (20) (0) Y
INSPECTION COMMENTS: CONTRACTOR DID NOT SHOW TO SCHEDULED INSPECTION.
 
(6) 09/01/2017 09/01/2017 PHG V R (100) (3)
INSPECTION COMMENTS: DID NOT INSPECT ELEVATOR
 
(7) 12/18/2017 12/18/2017 PHG N (25) (0) Y
INSPECTION COMMENTS: ENTERED ZARA STORE MET WITH MANGER LOOKED FOR CONTRACTOR. COULD NOT LOCATE CONTRACTOR. CALLED CONTRACTOR NO ANSWER. NO SHOW
 
(8) 01/23/2018 01/24/2018 PHG N (30) (0) Y
INSPECTION COMMENTS: ENTERED ZARA SPOKE WITH MANGER MANGER UNAWARE OF ELECTRICIAN ON SITE. CONTRACTOR NO SHOW
 
(9) 02/08/2018 02/08/2018 EDB V R (65) (2)
INSPECTION COMMENTS: SEE ATTACHMENT. INSPECT CELLAR.
 
(10) 03/29/2018 03/30/2018 TOR C R (85) (0)
INSPECTION COMMENTS: PASS SEE APP M 400919 FOR LIGHTS

OBJECTION FOR APPLICATION #: M373082
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS) PANELS: ARCH FLASH WARNING LABELS T-OUT.. 110.16
RSLV 10/30/2015 10/30/2015 01/06/2016
 
002 (999) OTHER
(ALL FLOORS) PANELS: 288/480 STICKERS MISSING T-OUT.. 408.60
RSLV 10/30/2015 10/30/2015 09/21/2016
 
003 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(ALL FLOORS)SERVICE: CELLAR SERVICE & MDPS NOT MATCHINH ADVISORY DRAWING FOR ALLMDPS,TRANSFORMERS,RISERS
RSLV 10/30/2015 10/30/2015 09/21/2016
 
004 (999) OTHER
(ALL FLOORS)EL RMS: FIRE STOP NOT PROVIDED ALL PENETRATIONS.. 300.21
RSLV 10/30/2015 10/30/2015 01/06/2016
 
005 (999) OTHER
(ALL FLOORS)EL RMS: NEED DIVIDER FOR SEPARATION 110V & 277 & 480 IN CROWN BOX300.3C1A
RSLV 10/30/2015 10/30/2015 01/06/2016
 
006 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
(ALL FLOORS)T-OUT: KOS MISSING ABOUT PANELS & STORAGE AREA 2ND FLR.. 110.12A
RSLV 10/30/2015 10/30/2015 01/06/2016
 
007 ( 29) OUTLET BOXES ARE NOT COVERED
(ALL FLOORS) T-OUT: COVERS MISSING BOXES T-OUT.. 314.25
RSLV 10/30/2015 10/30/2015 01/06/2016
 
008 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
(ALL FLOORS) T-OUT: EMT SUPPORTS NOT ADEQUATE.. 358.30
RSLV 10/30/2015 10/30/2015 09/21/2016
 
009 ( 17) DEFECTIVE SWITCHES ARE IN USE
(ALL FLOORS) MECH.RM: DEFECTIVE PILOT LT SW CHILLER RM.. 110.2A
RSLV 10/30/2015 10/30/2015 09/21/2016
 
010 (999) OTHER
(ALL FLOORS) MECH.RM: ZIP SCREW FOR GROUND.. 250.8
RSLV 10/30/2015 10/30/2015 01/06/2016
 
011 (999) OTHER
(ALL FLOORS) MECH.RM: 400 AMP DISCONNECT NEEDS MIGBS.. 250.64
RSLV 10/30/2015 10/30/2015 09/21/2016
 
012 ( 15) FLEXIBLE CORDS USED AS PERMANENT WIRING METHOD
(ALL FLOORS)CEILING: CONDENSATE WIRED W/FLEX CORD & EXTENSION CORDS.. 400.8
RSLV 10/30/2015 10/30/2015 09/01/2017
 
013 (271) BONDING INSUFFICIENT, OVER 250 VOLTS
(ALL FLOORS)T-OUT: BONDING NOT SUFFICIENT VOLTAGE OVER 250 VOLTS.. 250.97
RSLV 10/30/2015 10/30/2015 01/06/2016
 
014 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(FLOOR: 002) EL. RM. : NOT APPROVED GND CONNECTION FOR 225KVA T-FMR
RSLV 01/06/2016 01/06/2016 09/01/2017
 
015 (124) TAP CONDUCTORS ARE NOT WITHIN 10 FT OR WITHIN 25 FT AS PER CODE
(CELLAR)CEL A LEVEL: FROM1200 A FUSE TAP OVER 10' FOR F/A T-FMR , WIRE SIZEAND TAP FROM ONE SET ONLY
RSLV 01/06/2016 01/06/2016 09/01/2017
 
016 (128) NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH
(CELLAR) 400 AMP SW NEUTRAL BONDED 250.24
RSLV 09/01/2017 09/01/2017 02/08/2018
 
017 (128) NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH
(CELLAR) FA SW NEUTRAL BONDED 250.24
RSLV 09/01/2017 09/01/2017 02/08/2018
 
018 ( 19) DEFECTIVE WIRING IS IN USE
(CELLAR) IMPROPER TAP OF PARALLEL CONDUCTORS 300.3
RSLV 09/01/2017 09/01/2017 02/08/2018
 
019 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(CELLAR)F/A T-FMR DISC. SW. : UNDERSIZE EQUIPMENT GND (TAP FROM 1200 A)250.122
RSLV 02/08/2018 02/08/2018 03/29/2018
 
020 ( 45) FIXTURE NOT INSTALLED IN AN APPROVED MANNER
(CELLAR) CEILING LIGHT FIXTURES NOT PROPERLY SECURED410.30,36
RSLV 02/08/2018 02/08/2018 03/29/2018