Premises: 13 EAST 13 STREET MANHATTAN BIN: 1083135     Block: 571   Lot: 7501
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 13 E 13 ST Census Tract:   61 Health Area:  5700
2ND Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10003 Community Board:   102
DOB Cross Street(s):    5 AVENUE,    UNIVERSITY PLACE
Status:   C - JOB IS SIGNED OFF 09/16/2019 Balance Paid By Owner
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/29/2015 9:23 PM
Application Entered:   09/29/2015 Job Start Date:   09/30/2015
Last Change:   09/16/2019 Job End Date:   12/30/2015
Appointment Status:   
Last Inspection By:   SCHULER, THOMAS       On     02/19/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012067 Licensee Name: MICHAEL K PETERSON
Firm: 003761 Firm Name: MKP ELECTRIC CORP
Firm Phone: 718-783-0103  Firm Address: 733 FRANKLIN AVENUE BROOKLYN NY 11238 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $100.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   SALON
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: REYNALD RICARD
Owner Business Name: REYNALD RICARD
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
002    12  25    15               
Buildings Total 12  25    15                  
Total Units : 52 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 11/02/2015
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  THE WORK WAS COMPLETED BY ANOTHER ELECTRICIAN HOWEVER THEREWAS NO PERMIT,HENCE NO INSPECTION.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M373014
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/26/2015 11/02/2015 BUR V (60) (6) Y
INSPECTION COMMENTS: ONLY PANEL INPECTED,CONTRACTOR DOES NOT KNOW SCOPE OF WORK,APP NEEDS TO BE AMENDED
 
(2) 02/19/2016 02/23/2016 TUR C R (35) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED, SEE APP M314715

OBJECTION FOR APPLICATION #: M373014
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS)PANEL: BRANCH CKT CONDUCTORS NOT TERMINATED ON APPROPRIATE BREAKERS240.4
RSLV 10/26/2015 10/26/2015 02/19/2016
 
002 (999) OTHER
(ALL FLOORS)PANEL: NEUTRAL BONDED BEYOND MAIN SERVICE SWITCH.. 250.24
RSLV 10/26/2015 10/26/2015 02/19/2016
 
003 (999) OTHER
(ALL FLOORS) PANEL: MULTIWIRE CKTS NOT TERMINATED PROPERLY.. 210.4
RSLV 10/26/2015 10/26/2015 02/19/2016
 
004 (999) OTHER
(ALL FLOORS)PANEL: EQUIPMENT GROUPING CONDUCTORS DOUBLED UNDER ONE LUG.. 110.14
RSLV 10/26/2015 10/26/2015 02/19/2016
 
005 (999) OTHER
(ALL FLOORS) PANEL: EMT CONDUITS NOT PROPERLY SECURED.. 350.30
RSLV 10/26/2015 10/26/2015 02/19/2016
 
006 (999) OTHER
(ALL FLOORS)PANEL: BRANCH CKT CONDUCTORS NOT PROPERLY COLOR CODED.. 250.119,210.5B
RSLV 10/26/2015 10/26/2015 02/19/2016