BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M372793
Premises: 232 7 AVENUE MANHATTAN BIN: 1090490     Block: 773   Lot: 44
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 232 7 AV Census Tract:   91 Health Area:  5200
232 7TH AVENUE CCE635,CCE636 Admin Area:   M - MANHATTAN Inspection Area:   P
NEW YORK, NY 10011 Community Board:   104
Related Job Number:    121040729
DOB Cross Street(s):   WEST 23 STREET,    WEST 24 STREET
Status:   C - JOB IS SIGNED OFF 11/26/2019 Balance Paid By Owner
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/24/2015 1:02 PM
Application Entered:   09/24/2015 Job Start Date:   03/06/2016
Last Change:   11/26/2019 Job End Date:   10/10/2017
Appointment Status:   
Last Inspection By:   CONROY BLAKE       On     11/18/2019      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010552 Licensee Name: JOSEPH H BRAMAN
Firm: 004092 Firm Name: TK ELEVATOR CORPORATION
Firm Phone: 212-947-8800  Firm Address: 519 8TH AVENUE, 6TH FL NEW YORK NY 10018 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $456.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   V1-VACANT LAND
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: SABAH SHEMEL
Owner Business Name: CHELSEA 7 JV LLC
Authorized Representative:  SABAH SHEMEL
Relationship To Owner:   OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  2  
B. Each Additional 10 Floors Or Less  2  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: C - CALL TO OFFICE 10/29/2019
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M372793
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/03/2019 06/03/2019 MJD V (55) (3)
INSPECTION COMMENTS: FAIL, OBJECTIONS ISSUED
 
(2) 08/19/2019 08/19/2019 MJD H X (40) (0) Y
INSPECTION COMMENTS: FAIL, NO PROGRESS ON JOB, PLEASE HAVE ELECTRICIAN PRESENT FOR THIS INSPECTION,
 
(3) 08/23/2019 08/24/2019 MJD N (30) (0) Y
INSPECTION COMMENTS: FAIL, NO SHOW CALLED CONTRACTOR
 
(4) 09/23/2019 09/23/2019 CBK V Y (45) (1)
INSPECTION COMMENTS: OBJECTIONS PARTIALLY REMOVED.
 
(5) 10/11/2019 10/11/2019 ASK J Y (50) (0)
INSPECTION COMMENTS: FAIL. JOB IN PROGRESS.
 
(6) 10/28/2019 10/29/2019 DWB V X (41) (3)
INSPECTION COMMENTS: OBJECTION ISSUED.
 
(7) 11/18/2019 11/18/2019 CBK C R (35) (0)
INSPECTION COMMENTS: OBJECTIONS RESOLVED.

OBJECTION FOR APPLICATION #: M372793
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ROOF) NEUTRALS RUN THRU SWITCH FOR CAB LIGHTS ART. 620.53
RSLV 06/03/2019 06/03/2019 09/23/2019
 
002 (999) OTHER
(ROOF)OCP NOT PROVIDED FOR CONDUCTORS ON THE SECONDARY SIDE OF TRANSFORMERART. 240.21
RSLV 06/03/2019 06/03/2019 11/18/2019
 
003 (999) OTHER
(ROOF) TRANSFORMERS NOT GROUNDED ART. 250.30
RSLV 06/03/2019 06/03/2019 09/23/2019
 
004 (999) OTHER
(ROOF) TRANSFORMER PRIMARY OVER-FUSED. 450.4
RSLV 09/23/2019 09/23/2019 10/11/2019
 
005 ( 33) KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX
(ROOF) 110.12(A), KO NOT INSTALLED, AT ELEVATOR CONTROLLER
RSLV 10/28/2019 10/28/2019 11/18/2019
 
006 (999) OTHER
(ROOF)250.96, 277 VOLT, KO, GENERAL BONDING SHALL BE PROVIDED, WHERENECESSARY FOR ELECTRICAL CONTINUITY.
RSLV 10/28/2019 10/28/2019 11/18/2019
 
007 (999) OTHER
(ROOF) 348.60, FMC BONDING JUMPER REQUIRE.
RSLV 10/28/2019 10/28/2019 11/18/2019