BIS Menu  |  After Hours Variance Permits  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M372611
Premises: 202 CANAL STREET MANHATTAN BIN: 1082488     Block: 200   Lot: 7502
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 202 CANAL ST Census Tract:   29 Health Area:  7700
SUITE 601 Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10013 Community Board:   103
DOB Cross Street(s):   MOTT STREET,    MULBERRY STREET
Status:   C - JOB IS SIGNED OFF 07/27/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/20/2015 9:11 PM
Application Entered:   09/20/2015 Job Start Date:   09/21/2015
Last Change:   07/27/2017 Job End Date:   11/21/2015
Appointment Status:   
Last Inspection By:   GANITIS, PHILLIP       On     07/07/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012702 Licensee Name: ALLAN TANG
Firm: 004539 Firm Name: A ELECTRICAL MAIN SVC INC
Firm Phone: 718-234-9250  Firm Address: 198 AVENUE S, 1ST FLOOR BROOKLYN NY 11223 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $49.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MICHAEL MUI
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
004      21    18             
Buildings Total   21    18                
Total Units : 46 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 05/18/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M372611
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/15/2017 05/18/2017 STP V (35) (6)
INSPECTION COMMENTS: FAIL. WORK INSPECTED WAS 405 SUITE 4TH FLOOR, WRONG SUITE ON APP. CONTRACTOR STATED PANEL WAS EXISTING.
 
(2) 07/07/2017 07/10/2017 PHG C R (30) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED

OBJECTION FOR APPLICATION #: M372611
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 004) BOXS WITH MC GROUND WITH ZIPPIES TOUT 250.8
RSLV 05/15/2017 05/15/2017 07/07/2017
 
002 (999) OTHER
(FLOOR: 004) MC IN PANEL NOT TERMINATED ALL 250.148
RSLV 05/15/2017 05/15/2017 07/07/2017
 
003 (999) OTHER
(FLOOR: 004) CEILING BOX NOT SUPPORTED 314.23
RSLV 05/15/2017 05/15/2017 07/07/2017
 
004 (999) OTHER
(FLOOR: 004) CEILING BOXS NEED BX CONNECTORS 320.40
RSLV 05/15/2017 05/15/2017 07/07/2017
 
005 (999) OTHER
(FLOOR: 004) NO WIRE NUTS FOR GROUNDS TOUT 110
RSLV 05/15/2017 05/15/2017 07/07/2017
 
006 (999) OTHER
(FLOOR: 004) SOME LIGHTS NEED SUPPORT LAY IN 410.36
RSLV 05/15/2017 05/15/2017 07/07/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  After Hours Variance Permits  |  Electrical Inspection Work Order  |  Back