BIS Menu  |  Electrical Applications  |  After Hours Variance Permits  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M372582
Premises: 436 EAST 13 STREET MANHATTAN BIN: 1090881     Block: 440   Lot: 26
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 436 E 13 ST Census Tract:   34 Health Area:  6200
1 FL Admin Area:   M - MANHATTAN Inspection Area:   T
NEW YORK, NY 10009 Community Board:   103
DOB Cross Street(s):    1 AVENUE,    AVENUE A
Status:   C - JOB IS SIGNED OFF 12/11/2020
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/18/2015 3:29 PM
Application Entered:   09/18/2015 Job Start Date:   09/18/2015
Last Change:   12/11/2020 Job End Date:   09/17/2016
Appointment Status:   
Last Inspection By:   SHERON MEYERS       On     12/06/2020      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011878 Licensee Name: EDGAR LEVENSTEIN
Firm: 003500 Firm Name: CONTACT PLUS ELEC'L CORP
Firm Phone: 718-254-0291  Firm Address: 2922 SHELL ROAD BROOKLYN NY 11224 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
2 - TEMPORARY CONSTRUCTION
Total Fee:  $315.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: DAVID AMIRIAN
Owner Business Name: BRIDGETON AMIRIAN 13TH ST
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  300 AMP, COMBO
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  #3/0 AWG
D. Over 250 MCM  1  350 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  200 AMP
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 09/18/2015 Notice: 1 - FIRST NOTICE 08/21/2020
Power Issued: 09/18/2015 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M372582
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/20/2020 08/21/2020 SWR V (45) (2)
INSPECTION COMMENTS: FAIL. INSPECTION COMPLETE. OBJECTION ISSUED. CONTRACTOR SHOWED UP AT 10:15 AM. LMB ELECTRICAL WILL TAKE OVER ALL OBJECTIONS FROM APPLICATION # M372582, AND NEED TO FILE NEW APP FOR OBJECTIONS ONLY.
 
(2) 12/06/2020 12/06/2020 SWR C R (60) (0)
INSPECTION COMMENTS: PASS. INSPECTION COMPLETE. WITH APP NUMBER M00423250. ALL OBJECTIONS REMOVED.

OBJECTION FOR APPLICATION #: M372582
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (269) FIRE PUMP SUPPLY CONDUCTORS NOT PROPERLY INSTALLED
(BASEMENT)(FIRE PUMP) EMT IN USE AT FIRE PUMP TO MOTOR IN SEPARATE ROOM. AM695.6
RSLV 08/20/2020 08/20/2020 12/06/2020
 
002 (272) EQUIPMENT GROUNDING CONDUCTOR NOT PROPERLY INSTALLED
(BASEMENT) MAIN BUILDING GROUND (COLLECTOR BAR) NOT VISIBLE. 250.52
RSLV 08/20/2020 08/20/2020 12/06/2020



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Applications  |  After Hours Variance Permits  |  Electrical Inspection Work Order  |  Back