BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M372474
Premises: 67 SPRING STREET MANHATTAN BIN: 1079953     Block: 496   Lot: 36
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 67 SPRING ST Census Tract:   43 Health Area:  6800
FIRST FL. Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10012 Community Board:   102
Special Place Name:   JOE THE JUICE
DOB Cross Street(s):   CLEVELAND PLACE,    CROSBY STREET
Status:   C - JOB IS SIGNED OFF 04/26/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/16/2015 7:15 PM
Application Entered:   09/16/2015 Job Start Date:   09/17/2015
Last Change:   04/26/2016 Job End Date:   09/17/2016
Appointment Status:   
Last Inspection By:   MOSES, DANIEM       On     02/10/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012463 Licensee Name: DIMITRIOS K TOMBORIS
Firm: 004270 Firm Name: CAD ELECTL CONTNG SVC CO
Firm Phone: 718-353-3654  Firm Address: 7-16 COLLEGE POINT BLVD COLLEGE POINT NY 11356 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $224.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   RESTAURANT
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: CASEY MARTINEZ
Owner Business Name: UNITED AMERICAN LLC
Authorized Representative:  CASEY MARTINEZ
Relationship To Owner:   PARTNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  4#3/0 2" CONDUIT
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  225 A 42 CKT
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    150  49    17  150             
Buildings Total 150  49    17  150                
Total Units : 366 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 11/19/2015
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  JOE THE JUICE

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M372474
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/12/2015 11/19/2015 PHG V (75) (6) Y
INSPECTION COMMENTS: CONTRACTOR LATE - UNAWARE OF SCOPE OF WORK - FULL INSPECTION NEEDED BSMT ONLY INSPECTED
 
(2) 02/10/2016 02/11/2016 DNM C R (27) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED.

OBJECTION FOR APPLICATION #: M372474
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(ALL FLOORS) BSMT: #8 WIRE ON 60 AMP BREAKER IN BSMT PANEL.. 240.3
RSLV 11/12/2015 11/12/2015 02/10/2016
 
002 (999) OTHER
(ALL FLOORS) BSMT: NO 90* SWING ON WATER HEATER DISCONNECT.. 110.26
RSLV 11/12/2015 11/12/2015 02/10/2016
 
003 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
(ALL FLOORS) BSMT: EMT NOT SUPPORTED IN BSMT
RSLV 11/12/2015 11/12/2015 02/10/2016
 
004 (999) OTHER
(ALL FLOORS)OUTSIDE: 30 AMP A/C DISCONNECT OUTSIDE NO BOND.. 250.112
RSLV 11/12/2015 11/12/2015 02/10/2016
 
005 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(ALL FLOORS)BSMT: NO GRND IN BACK BSMT RM FOR FMC IN A/C SW.. 250.122
RSLV 11/12/2015 11/12/2015 02/10/2016
 
006 ( 3) APPLICATION FOR CERTIFICATE OF ELECTRICAL INSPECTION NOT ON FILE
(ALL FLOORS) BSMT: NO A/C,HEATER OR 400 AMP PANEL/FEEDER APP ON FILE
RSLV 11/12/2015 11/12/2015 02/10/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back