BIS Menu  |  After Hours Variance Permits  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M372427
Premises: 60 EAST 88 STREET MANHATTAN BIN: 1046927     Block: 1499   Lot: 7501
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 62 E 88 ST Census Tract:   150.02 Health Area:  3600
BASEMENT Admin Area:   M - MANHATTAN Inspection Area:   J
NEW YORK, NY 10128 Community Board:   108
DOB Cross Street(s):   MADISON AVENUE,    PARK AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/16/2015 8:33 AM
Application Entered:   09/16/2015 Job Start Date:   09/16/2015
Last Change:   08/22/2025 Job End Date:   09/14/2016
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   RAMJAG, BUDRAM       On     06/08/2016      
Field Disp:   J - JOB IN PROGRESS
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  X - NOT REMOVED

License #: 012570 Licensee Name: DONALD C JACKSON
Firm: 004078 Firm Name: NABER ELECTRIC, N.Y. CORP
Firm Phone: 718-708-7690  Firm Address: 3471 STEENWICK AVENUE BRONX NY 10475 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $465.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MIKE COLAROSSI
Owner Business Name: SIMONE DEVELOPMENT
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  1  2 SETS 500 MCM
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  4  4 #3/0
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 4 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 09/16/2015 Notice: C - CALL TO OFFICE 06/10/2016
Power Issued: 09/16/2015 Response:  

Follow-Up:
Contractor's Comments:  FEEDERS TO 4 POWER PANELS

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M372427
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/03/2015 12/04/2015 TOR V G (90) (4) Y
INSPECTION COMMENTS: GENERAL WIRING NOT READY FOR INSPECTION
 
(2) 01/10/2016 01/11/2016 TSO J R E (1) (0) Y
INSPECTION COMMENTS: NONE
 
(3) 01/11/2016 01/11/2016 TSO V (2) (4)
INSPECTION COMMENTS: IN OFFICE
 
(4) 06/08/2016 06/10/2016 BUR J X (45) (0) Y
INSPECTION COMMENTS: NOT READY FOR INSPECTION

OBJECTION FOR APPLICATION #: M372427
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
SUB-CELL: SERVICE NOT PROPERLY BONDED.. 250.92(A)
RSLV 12/03/2015 12/03/2015 01/10/2016
 
002 ( 4) SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL
SUB-CELL: NO ADVISORY BOARD APPROVAL.. 110.2
RSLV 12/03/2015 12/03/2015 01/10/2016
 
003 (999) OTHER
SUB-CELL: ARC FLASH WARNINGS.. 110.16
RSLV 12/03/2015 12/03/2015 01/10/2016
 
004 (999) OTHER
SUB-CELL: NO WATER MAIN SUPPLEMENTAL GROUND.. 250.24
RSLV 12/03/2015 12/03/2015 01/10/2016
 
005 ( 4) SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL
(CELLAR) NO ADVISORY APPROVAL
OPEN 01/11/2016 01/11/2016
 
006 (999) OTHER
(CELLAR) SERVICE NOT BONDED
OPEN 01/11/2016 01/11/2016
 
007 (999) OTHER
(CELLAR) NO ARC FLASH LABELS
OPEN 01/11/2016 01/11/2016
 
008 (999) OTHER
(CELLAR) NO WATER OR SUP GND
OPEN 01/11/2016 01/11/2016