Electrical Application Details for App #: M372354
Premises: 2 EAST 52 STREET MANHATTAN BIN: 1035479     Block: 1287   Lot: 69
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 2 E 52 ST Census Tract:   102 Health Area:  4800
CORNER OF 52ND STREET Admin Area:   M - MANHATTAN Inspection Area:   L
NEW YORK, NY 10022 Community Board:   105
Special Place Name:   CARTIER
DOB Cross Street(s):    5 AVENUE,    MADISON AVENUE
Status:   C - JOB IS SIGNED OFF 06/21/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/14/2015 3:42 PM
Application Entered:   09/14/2015 Job Start Date:   09/14/2015
Last Change:   06/21/2018 Job End Date:   12/31/2016
Appointment Status:   
Last Inspection By:   SCHULER, THOMAS       On     06/21/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010710 Licensee Name: MARC CUSUMANO
Firm: 002039 Firm Name: ARCADIA ELECT'L CO. INC.
Firm Phone: 718-418-0106  Firm Address: 1005 WYCKOFF AVENUE RIDGEWOOD NY 11385 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $5,040.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   JEWERLY STORE
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   52767     Submittal #: 15A0087  
Owner / Occup: FRANK NALIBOFF
Owner Business Name: DICKINSON CAMERON CONSTRU
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  60A
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  600A FIRE PUMP
D. 601 Up to 1200 AMPS  1  800A
E. Over 1200 AMPS  2  1-1200A 1-2500A
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  20  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  15  500MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  20  
D. 3 Phase Over 225 AMPS  6  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
SUB    213  67    38  213         
CEL    202  82    35  202             
001    279  59    20  279             
002    369  33    17  369             
003    387  77    25  387             
004    335  60    17  335             
005    323  64    29  323             
006    201  146    40  201             
ROF          30         
Buildings Total 2309  590    223  2309     35           
Total Units : 5466 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 2
Existing Meters 2 + New Meters 2 - Removed Meters 2 = Total Meters 2

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 09/14/2015 Notice: 1 - FIRST NOTICE 03/12/2018
Power Issued: 09/14/2015 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  N/A

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M372354
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/09/2018 03/12/2018 RDI V (195) (4)
INSPECTION COMMENTS: INSP.COMPLETED. BOTH SERVICE ROOMS #2, #4 E 52 ST AND ALL FLOORS.
 
(2) 06/21/2018 06/21/2018 TUR J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-18-000009391
 
(3) 06/21/2018 06/21/2018 TUR J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-18-000009392
 
(4) 06/21/2018 06/21/2018 TUR J Y (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-18-000009393
 
(5) 06/21/2018 06/21/2018 TUR C R (0) (0)
INSPECTION COMMENTS: CERTIFIED - OBJ-18-000009394

OBJECTION FOR APPLICATION #: M372354
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(ALL FLOORS) ALL DISPLAY CASES
RSLV 03/09/2018 03/09/2018 06/21/2018
 
002 ( 25) ARMORED CABLES ARE NOT PROPERLY TERMINATED
(ALL FLOORS) ALL DISPLAY CASES
RSLV 03/09/2018 03/09/2018 06/21/2018
 
003 ( 27) ARMORED CABLES INSTALLED WITHOUT INSULATING BUSHINGS
(ALL FLOORS) ALL DISPLAY CASES.
RSLV 03/09/2018 03/09/2018 06/21/2018
 
004 (999) OTHER
(ALL FLOORS)NO LISTINGS PROVIDED FOR ALL CUSTOM MADE DISPLAY CASES. (110.2 -110.3)
RSLV 03/09/2018 03/09/2018 06/21/2018