Electrical Application Details for App #: M372216
Premises: 225 BOWERY MANHATTAN BIN: 1089461     Block: 426   Lot: 5
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 225 BOWERY Census Tract:   36.01 Health Area:  6500
ENTIRE BUILDING Admin Area:   M - MANHATTAN Inspection Area:   T
NEW YORK, NY 10002 Community Board:   103
DOB Cross Street(s):   RIVINGTON STREET,    PRINCE STREET
Status:   C - JOB IS SIGNED OFF 02/11/2019
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/10/2015 2:33 PM
Application Entered:   09/10/2015 Job Start Date:   09/10/2015
Last Change:   02/11/2019 Job End Date:   09/10/2018
Appointment Status:   
Last Inspection By:   VAZQUEZ, LOUIS       On     02/11/2019      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012022 Licensee Name: JOSEPH SORTINO
Firm: 003742 Firm Name: TOP SHELF ELECTRIC CORP
Firm Phone: 718-815-1700  Firm Address: 3917 AMBOY ROAD STATEN ISLAND NY 10308 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $4,349.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   H - Hotel
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: DAVID S PAZ
Owner Business Name: AEH-VSLV, LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  2  2X 400 AMPS
D. 601 Up to 1200 AMPS  3  2X 800 AMPS 1X 1200 AMPS
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  6  6 SETS OF 4 #500 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  29  25X 125 AMPS 4X 225 AMPS
D. 3 Phase Over 225 AMPS  4  2X 800 1X 1200 1X 2500
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
SUB      11  33             
CEL    50  14    24  139  14     
001    40  105    11  171  49  13     
002    52  61    60  157  20  20         
003    51  67    67  161  20  20         
004    52  66    66  159  20  20         
005    52  66    66  159  20  20         
006    52  66    66  159  20  20         
007    52  66    67  161  20  20         
008    52  66    67  161  20  20         
009    52  66    67  161  20  20         
010    52  66    67  161  20  20         
011    35  25    120  15         
012    21  21    21  58  25         
013    21  21    21  58  25         
014    21  21    21  58  25         
ROF        25  11  260  21     
Buildings Total 659  806    711  2101     582     48      
Total Units : 4907 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 1
Existing Meters 1 + New Meters 2 - Removed Meters 1 = Total Meters 2

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 09/10/2015 Notice: 1 - FIRST NOTICE 01/28/2019
Power Issued: 09/10/2015 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M372216
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/25/2019 01/28/2019 MJD V (215) (9)
INSPECTION COMMENTS: FAIL, ALL ROOMS INSPECTED OK, BASEMENT, SERVICE ROOM, HALLWAYS AND ROOF INSPECTED OBJECTIONS ISSUED, 11 FLOOR BAR AND 1 FLOOR RESTAURANT AND LOBBY NOT FINISHED NOT INSPECTED.
 
(2) 02/11/2019 02/11/2019 LV1 C R (65) (0)
INSPECTION COMMENTS: PASS. 1ST FL AND 11TH FLOOR BAR FILED UNDER DIFFERENT APP SEE M00127838I1EL

OBJECTION FOR APPLICATION #: M372216
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 29) OUTLET BOXES ARE NOT COVERED
(ALL FLOORS) BASEMENT, ROOF, 1 FLOOR, 11 FLOOR
RSLV 01/25/2019 01/25/2019 02/11/2019
 
002 ( 42) BUSHINGS ARE MISSING OR LOOSE
(ALL FLOORS) T-OUT PANELS ART. 300.4
RSLV 01/25/2019 01/25/2019 02/11/2019
 
003 (999) OTHER
(ALL FLOORS)MC CABLE GROUND CONDUCTOR NOT BONDED IN SPLICE BOXES, BAS. KITCHENROOF SPLICE BOX ART. 250.118
RSLV 01/25/2019 01/25/2019 02/11/2019
 
004 (999) OTHER
(ALL FLOORS)ARC FLUSH WARNING STICKERS NOT PROVIDED T-OUT ART. 110.16
RSLV 01/25/2019 01/25/2019 02/11/2019
 
005 (999) OTHER
(ALL FLOORS)TEMPORARY CONSTRUCTION WIRING NOT REMOVED T-OUT BUILDING ART. 590.3
RSLV 01/25/2019 01/25/2019 02/11/2019
 
006 (999) OTHER
(ALL FLOORS) OPEN KO T-OUT PANELS ART. 110.12
RSLV 01/25/2019 01/25/2019 02/11/2019
 
007 ( 30) OUTLET BOXES ARE NOT SECURED
(BASEMENT) BASEMENT KITCHEN ART. 314.23
RSLV 01/25/2019 01/25/2019 02/11/2019
 
008 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
(BASEMENT) WATER MAIN GROUND AND SUPPLEMENTAL GROUND ART. 250.24
RSLV 01/25/2019 01/25/2019 02/11/2019
 
009 (999) OTHER
(BASEMENT)COMMERCIAL KITCHEN RECEPTACLES NOT GFCI PROTECTED ART. 210.8
RSLV 01/25/2019 01/25/2019 02/11/2019