| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
2 |
2X 400 AMPS |
| D. 601 Up to 1200 AMPS |
3 |
2X 800 AMPS 1X 1200 AMPS |
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
6 |
6 SETS OF 4 #500 MCM |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
29 |
25X 125 AMPS 4X 225 AMPS |
| D. 3 Phase Over 225 AMPS |
4 |
2X 800 1X 1200 1X 2500 |
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 29) |
OUTLET BOXES ARE NOT COVERED (ALL FLOORS) BASEMENT, ROOF, 1 FLOOR, 11 FLOOR |
RSLV |
01/25/2019 |
01/25/2019 |
02/11/2019 |
| |
| 002 |
( 42) |
BUSHINGS ARE MISSING OR LOOSE (ALL FLOORS) T-OUT PANELS ART. 300.4 |
RSLV |
01/25/2019 |
01/25/2019 |
02/11/2019 |
| |
| 003 |
(999) |
OTHER (ALL FLOORS)MC CABLE GROUND CONDUCTOR NOT BONDED IN SPLICE BOXES, BAS. KITCHENROOF SPLICE BOX ART. 250.118 |
RSLV |
01/25/2019 |
01/25/2019 |
02/11/2019 |
| |
| 004 |
(999) |
OTHER (ALL FLOORS)ARC FLUSH WARNING STICKERS NOT PROVIDED T-OUT ART. 110.16 |
RSLV |
01/25/2019 |
01/25/2019 |
02/11/2019 |
| |
| 005 |
(999) |
OTHER (ALL FLOORS)TEMPORARY CONSTRUCTION WIRING NOT REMOVED T-OUT BUILDING ART. 590.3 |
RSLV |
01/25/2019 |
01/25/2019 |
02/11/2019 |
| |
| 006 |
(999) |
OTHER (ALL FLOORS) OPEN KO T-OUT PANELS ART. 110.12 |
RSLV |
01/25/2019 |
01/25/2019 |
02/11/2019 |
| |
| 007 |
( 30) |
OUTLET BOXES ARE NOT SECURED (BASEMENT) BASEMENT KITCHEN ART. 314.23 |
RSLV |
01/25/2019 |
01/25/2019 |
02/11/2019 |
| |
| 008 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY (BASEMENT) WATER MAIN GROUND AND SUPPLEMENTAL GROUND ART. 250.24 |
RSLV |
01/25/2019 |
01/25/2019 |
02/11/2019 |
| |
| 009 |
(999) |
OTHER (BASEMENT)COMMERCIAL KITCHEN RECEPTACLES NOT GFCI PROTECTED ART. 210.8 |
RSLV |
01/25/2019 |
01/25/2019 |
02/11/2019 |