BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M372100
Premises: 26 BLEECKER STREET MANHATTAN BIN: 1008186     Block: 521   Lot: 37
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 26 BLEEKER ST Census Tract:   55.02 Health Area:  5700
MOTOR ROOM Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10012 Community Board:   102
DOB Cross Street(s):   ELIZABETH STREET,    MOTT STREET
Status:   C - JOB IS SIGNED OFF 12/27/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/08/2015 3:31 PM
Application Entered:   09/08/2015 Job Start Date:   09/15/2015
Last Change:   12/27/2016 Job End Date:   12/31/2015
Appointment Status:   
Last Inspection By:   URIM SYLA       On     12/23/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010030 Licensee Name: JOHN R HOOVER
Firm: 000121 Firm Name: AMER. ELEVATOR & MACH. CO
Firm Phone: 718-784-0101  Firm Address: 36-36 33RD STREET, STE 104 LONG ISLAND CITY NY 11106 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $165.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: FREDERICO MORROBEL
Owner Business Name: PLANNED PARENTHOOED OF NY
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  1  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: C - CALL TO OFFICE 12/07/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M372100
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/27/2016 10/27/2016 CBK V (45) (2)
INSPECTION COMMENTS: SEE OBJECTION DETAILS.
 
(2) 12/06/2016 12/07/2016 CBK V X (45) (1)
INSPECTION COMMENTS: OBJECTION NOT REMOVED.
 
(3) 12/23/2016 12/27/2016 UMS C R (28) (0)
INSPECTION COMMENTS: OBJECTIONS CLEARED

OBJECTION FOR APPLICATION #: M372100
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 18) DEFECTIVE RECEPTACLES ARE IN USE
(BASEMENT) ELEVATOR CAR TOP, GFCI NOT WORKING PROPERLY.
RSLV 10/27/2016 10/27/2016 12/23/2016
 
002 (999) OTHER
(BASEMENT) SUMP-PUMP PLUG IN FFCI RECEPTACLE. AMEN. 620.24(A)
RSLV 10/27/2016 10/27/2016 12/23/2016
 
003 ( 19) DEFECTIVE WIRING IS IN USE
(ROOF) CAR LIGHT DISC. NEED NIPPLE
RSLV 12/06/2016 12/06/2016 12/23/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order