BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M371780
Premises: 185 MOTT STREET MANHATTAN BIN: 1007186     Block: 480   Lot: 33
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 58 KENMARE ST Census Tract:   41 Health Area:  6800
6,7,11,13,15 AND ROOF Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10012 Community Board:   102
DOB Cross Street(s):   MOTT STREET,    MULBERRY STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/30/2015 3:32 PM
Application Entered:   08/30/2015 Job Start Date:   08/30/2015
Last Change:   08/22/2025 Job End Date:   08/30/2016
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   BERGMAN EDUARD       On     06/17/2016      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 010939 Licensee Name: MICHAEL L ALPHONSE
Firm: 002249 Firm Name: BESTCO GENERAL ELEC. MAIN
Firm Phone: 718-324-5582  Firm Address: 922 EAST 233RD STREET BRONX NY 10466 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $310.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (4  Stores, 20 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MARC COHEN
Authorized Representative:  MARC COHEN
Relationship To Owner:   OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  10  60AMP. 1-PHASE
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  10  SET # 6
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
MZ1    15  18    10               
MZ2    15  18    10               
MZ3    15  18    10               
MZ4    15  18    10               
Buildings Total 60  72    40                  
Total Units : 172 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 06/21/2016
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  INSTALLING 10-A/C DISCONNECT ON ROOF,50-LIGHTS,75-OUTLETS,AND 40-SWITCHES ALL BRANCH CKT.ARE EXISTING

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M371780
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/17/2016 06/21/2016 EDB V (75) (6)
INSPECTION COMMENTS: P

OBJECTION FOR APPLICATION #: M371780
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (311) FIXTURE NOT APPROVED FOR DAMP/WET LOCATION
(ALL FLOORS) BATHROOM FIXTURE NOT APPROVED
OPEN 06/17/2016 06/17/2016
 
002 (999) OTHER
(ALL FLOORS) NO 2 CKT. FOR KITCHEN PROVIDED 210.52, 11 C.
OPEN 06/17/2016 06/17/2016
 
003 (999) OTHER
(ALL FLOORS) BATHROOM SWITCHES IN WET ZONE 404.4
OPEN 06/17/2016 06/17/2016
 
004 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(ROOF) LFMC MISSING EQUIPMENT GND 250.118
OPEN 06/17/2016 06/17/2016
 
005 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(ROOF) LFMC OVER 6' LONG AM.350.12
OPEN 06/17/2016 06/17/2016
 
006 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(ROOF) LFMC NOT SECURED 350.30
OPEN 06/17/2016 06/17/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Electrical Inspection Work Order  |  Back