| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
10 |
60AMP. 1-PHASE |
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
10 |
SET # 6 |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(311) |
FIXTURE NOT APPROVED FOR DAMP/WET LOCATION (ALL FLOORS) BATHROOM FIXTURE NOT APPROVED |
OPEN |
06/17/2016 |
06/17/2016 |
|
| |
| 002 |
(999) |
OTHER (ALL FLOORS) NO 2 CKT. FOR KITCHEN PROVIDED 210.52, 11 C. |
OPEN |
06/17/2016 |
06/17/2016 |
|
| |
| 003 |
(999) |
OTHER (ALL FLOORS) BATHROOM SWITCHES IN WET ZONE 404.4 |
OPEN |
06/17/2016 |
06/17/2016 |
|
| |
| 004 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED (ROOF) LFMC MISSING EQUIPMENT GND 250.118 |
OPEN |
06/17/2016 |
06/17/2016 |
|
| |
| 005 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED (ROOF) LFMC OVER 6' LONG AM.350.12 |
OPEN |
06/17/2016 |
06/17/2016 |
|
| |
| 006 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED (ROOF) LFMC NOT SECURED 350.30 |
OPEN |
06/17/2016 |
06/17/2016 |
|