| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(238) |
TEMP WIRING NOT REMOVED THROUGHOUT (BASEMENT) TEMP WIRING NOT REMOVED IN ROOM 590.3 |
RSLV |
01/07/2016 |
01/07/2016 |
02/08/2016 |
| |
| 002 |
( 33) |
KNOCKOUTS ARE NOT CLOSED IN OUTLET BOX (BASEMENT) CEILING BOX KO MISSING 110.12 |
RSLV |
01/07/2016 |
01/07/2016 |
02/08/2016 |
| |
| 003 |
(999) |
OTHER (BASEMENT)MICROWAVE OUTLET IN PANTRY NOT FLUSH COMBUSTIBLE WALL. 314.20 |
RSLV |
01/07/2016 |
01/07/2016 |
02/08/2016 |
| |
| 004 |
(999) |
OTHER (BASEMENT) HOT WATER HEATER OVER FUSED AT 30 AMPS 422.11 |
RSLV |
01/07/2016 |
01/07/2016 |
02/08/2016 |
| |
| 005 |
(238) |
TEMP WIRING NOT REMOVED THROUGHOUT (GROUND FLOOR) TEMP WIRING NOT REMOVED T OUT 590.3 |
RSLV |
01/07/2016 |
01/07/2016 |
02/08/2016 |
| |
| 006 |
( 29) |
OUTLET BOXES ARE NOT COVERED (GROUND FLOOR) RECEPTION AREA OUTLET PLATE BROKEN 406.4 C |
RSLV |
01/07/2016 |
01/07/2016 |
02/08/2016 |
| |
| 007 |
(999) |
OTHER (GROUND FLOOR)CEILING BOXS FOR LIGHTING NOT BONDED M.C. CABLE T OUT 250.148 |
RSLV |
01/07/2016 |
01/07/2016 |
02/08/2016 |
| |
| 008 |
(999) |
OTHER (GROUND FLOOR) X ROOM DISCONNECT NOT PROPERLY GROUNDED 250.4 |
RSLV |
01/07/2016 |
01/07/2016 |
02/08/2016 |