| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
4 |
3X4 - 1/0 &1X3-1/0 |
| D. Over 250 MCM |
5 |
2X& 4-400MCM |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
1 |
100AMP |
| D. 3 Phase Over 225 AMPS |
2 |
3 PHASE 600AMP |
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER (ALL FLOORS)BASE E.G.C BETWEEN XFMER DISC. AND INVERTER NOT AS PER 250.122 |
RSLV |
09/23/2015 |
09/23/2015 |
04/05/2016 |
| |
| 002 |
(212) |
NO GROUND PROVIDED FOR SEPARATELY DERIVED SYSTEM BASE XFMER |
OPEN |
09/23/2015 |
09/23/2015 |
|
| |
| 003 |
(999) |
OTHER BASE XFMR NO SYSTEM BONDING JUMP. 250.30 (A) |
OPEN |
09/23/2015 |
09/23/2015 |
|
| |
| 004 |
(999) |
OTHER BASE XFMR SECONDARY BONDING NOT AS PER 250.25 (D) |
OPEN |
09/23/2015 |
09/23/2015 |
|
| |
| 005 |
(999) |
OTHER (ALL FLOORS) BASE SECONDARY OF XFMR NOT FUSED AS 240.21 |
RSLV |
09/23/2015 |
09/23/2015 |
04/05/2016 |
| |
| 006 |
(132) |
EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED (ALL FLOORS) BASE CIRC. (30A)IN CONGEN AUX PANEL NOT AS PER 250.122 |
RSLV |
09/23/2015 |
09/23/2015 |
04/05/2016 |
| |
| 007 |
( 21) |
CONDUCTORS HAVE NOT BEEN PROPERLY DE-RATED (ALL FLOORS) BASE 100A COGEN AUX PANEL |
RSLV |
09/23/2015 |
09/23/2015 |
04/05/2016 |
| |
| 008 |
(132) |
EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED (ALL FLOORS) BASE E.G.C IN 600A SWITCH NOT AS PER 250.122 |
RSLV |
09/23/2015 |
09/23/2015 |
04/05/2016 |
| |
| 009 |
(999) |
OTHER (ALL FLOORS)BASE NO ARC FLASH AND 480V WARNING 110.16 AND 408.50 (C) |
RSLV |
09/23/2015 |
09/23/2015 |
04/05/2016 |
| |
| 010 |
( 19) |
DEFECTIVE WIRING IS IN USE (ALL FLOORS) BASE XF,R 2ND ARY OCPD NOT AS PER. 240.21 (C) |
RSLV |
09/23/2015 |
09/23/2015 |
04/05/2016 |
| |
| 011 |
(999) |
OTHER (ALL FLOORS)BASE NONCONUCTIVE COATING NOT REMOVED:EXISTING SERVICE EQUIPWITH NOW E.G.C LUGS 250.12 |
RSLV |
09/23/2015 |
09/23/2015 |
04/05/2016 |
| |
| 012 |
(109) |
SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED (BASEMENT) BETWEEN NEW 600A DISCONNECT & ENERGIZED PARTS OF EXISTING EQUIPMENT |
OPEN |
04/05/2016 |
04/05/2016 |
|
| |
| 013 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED (BASEMENT) XFMR INVERTER SIDE DISCONNECT BONDING SCREW NOT INSTALLED |
OPEN |
04/05/2016 |
04/05/2016 |
|
| |
| 014 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT) GENERATOR NOT GROUNDED |
OPEN |
04/05/2016 |
04/05/2016 |
|
| |
| 015 |
(999) |
OTHER (BASEMENT) NO WARNING ON XFMR PRIMARY & SECONDARY DISCONNECTS 404.6 (C) |
OPEN |
04/05/2016 |
04/05/2016 |
|