BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M371361
Premises: 18 THOMAS STREET MANHATTAN BIN: 1001654     Block: 151   Lot: 22
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 20 THOMAS ST Census Tract:   33 Health Area:  7700
. Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10007 Community Board:   101
Related Job Number:    121325315
DOB Cross Street(s):   BROADWAY,    TRIMBLE PLACE
Status:   C - JOB IS SIGNED OFF 05/19/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/19/2015 9:58 AM
Application Entered:   08/19/2015 Job Start Date:   10/01/2015
Last Change:   05/19/2017 Job End Date:   12/01/2015
Appointment Status:   
Last Inspection By:   CONROY BLAKE       On     05/04/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012297 Licensee Name: JOHN AHRENS
Firm: 004066 Firm Name: TUXEDO ELEC'L CONTR'G INC
Firm Phone: 718-786-0384  Firm Address: 10-32 47TH ROAD LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $165.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   THEATER
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: CAROL OSTROW
Owner Business Name: THE FLEA THEATER
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  1  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 04/20/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M371361
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/05/2017 04/06/2017 EDB N (30) (0) Y
INSPECTION COMMENTS: CALL CONTRACTOR, WANT TO RESCHEDULE . NO SHOW.
 
(2) 04/19/2017 04/20/2017 STP V (30) (3)
INSPECTION COMMENTS: CONTRACTOR NO SHOW. HAD ACCESS WITH GENERAL CONTRACTOR TO MOTOR ROOM. FULL INSPECT NEEDED.
 
(3) 05/04/2017 05/04/2017 CBK C R (45) (0)
INSPECTION COMMENTS: OBJECTION REMOVED.

OBJECTION FOR APPLICATION #: M371361
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ROOF) MOTOR DIS SW EGC BONDED TO NEUTRAL 250.24
RSLV 04/19/2017 04/19/2017 05/04/2017
 
002 (999) OTHER
(ROOF) MOTOR DIS SW EGC IDENTIFICATION 250.119
RSLV 04/19/2017 04/19/2017 05/04/2017
 
003 (999) OTHER
(ROOF) MOTOR DIS SW NEUTRAL IDENTIFICATION 200.6
RSLV 04/19/2017 04/19/2017 05/04/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order