BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M371008
Premises: 743 BROADWAY MANHATTAN BIN: 1080855     Block: 548   Lot: 7501
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 60 E 8 ST Census Tract:   57 Health Area:  5700
27F Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10003 Community Board:   102
DOB Cross Street(s):   MERCER STREET,    BROADWAY
Status:   C - JOB IS SIGNED OFF 02/17/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/10/2015 7:13 PM
Application Entered:   08/10/2015 Job Start Date:   08/11/2015
Last Change:   02/17/2016 Job End Date:   08/31/2015
Appointment Status:   
Last Inspection By:   SOLAVNTO, THOMAS       On     02/11/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012015 Licensee Name: MIECZYSLAW KARDASZ
Firm: 003926 Firm Name: MK ELECTRIC CONTR'S, INC
Firm Phone: 718-646-0128  Firm Address: 10 BAY 22ND STREET BROOKLYN NY 11214 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $123.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: LINDSAY RHOTEN
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  #8/3 BX
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  1  200A 100A-30 POLE
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
027  27F  40  20    30  37         
Buildings Total 40  20    30  37              
Total Units : 133 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 11/23/2015
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M371008
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/17/2015 11/23/2015 NRS A (70) (4) Y
INSPECTION COMMENTS: E&T APTS COMBINED WORK DONE IN ORIGINAL APT ONLY
 
(2) 12/10/2015 12/11/2015 EDB J R (25) (2)
INSPECTION COMMENTS: INSPECT OBJECTION ONLY.
 
(3) ? (0) (0)
INSPECTION COMMENTS: No Inspection Comments For This Application
 
(4) 02/11/2016 02/11/2016 TSO C (1) (0) Y
INSPECTION COMMENTS: AS PER EDB CERTIFY. DONE IN OFFICE

OBJECTION FOR APPLICATION #: M371008
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(ALL FLOORS) 27F: STEAM GEN&GEN DISCONNECT NOT AS PER 250.122
RSLV 11/17/2015 11/17/2015 12/10/2015
 
002 (220) DOUBLE LUGGING IN SERVICE SWITCH
(ALL FLOORS) 27F: RISER EXTENTION SPLICE BOX IN OFFICE
RSLV 11/17/2015 11/17/2015 12/10/2015
 
003 (999) OTHER
(ALL FLOORS) 27F: OUTLET BOXES SET TOO PEEP 314.20
RSLV 11/17/2015 11/17/2015 12/10/2015
 
004 (999) OTHER
(ALL FLOORS)27F: STEAM UNIT BRANCH CIRCUIT NOT SIZED AS PER MANU.S INSTRUCTIONS110.3
RSLV 11/17/2015 11/17/2015 12/10/2015
 
005 (311) FIXTURE NOT APPROVED FOR DAMP/WET LOCATION
(FLOOR: 027) OVER BATH TAB
RSLV 12/10/2015 12/10/2015
 
006 ( 6) FEEDER DIAGRAM DID NOT ACCOMPANY APPLICATION FOR INSPECTION
(FLOOR: 027) PANEL OVERLOAD ( NEED LOAD CALCULATION).
RSLV 12/10/2015 12/10/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order