BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M370959
Premises: 199 BOWERY MANHATTAN BIN: 1087253     Block: 425   Lot: 7502
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 199 BOWERY Census Tract:   18 Health Area:  7400
1 FLOOR KITCHEN Admin Area:   M - MANHATTAN Inspection Area:   V
NEW YORK, NY 10002 Community Board:   103
Special Place Name:   THE GENERAL
DOB Cross Street(s):   SPRING STREET,    RIVINGTON STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/09/2015 5:54 PM
Application Entered:   08/09/2015 Job Start Date:   08/10/2015
Last Change:   08/22/2025 Job End Date:   08/09/2016
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   PANAYOTEDIS, STEPHEN       On     07/12/2017      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 011514 Licensee Name: JOHN KAMBOURAKIS
Firm: 002985 Firm Name: MAR-KAM ELEC'L CONTR'G IN
Firm Phone: 718-833-7800  Firm Address: 153 32ND STREET BROOKLYN NY 11232 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $60.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   RESTAURANT
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: BILL PARLAMIS
Owner Business Name: MTC CONSTRUCTION
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    20  20    45             
Buildings Total 20  20    45                
Total Units : 90 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 07/12/2017
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M370959
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/12/2017 07/12/2017 STP V (30) (4)
INSPECTION COMMENTS: FAIL.

OBJECTION FOR APPLICATION #: M370959
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 001) CEILING BOXS OPEN 314.25
OPEN 07/12/2017 07/12/2017
 
002 (999) OTHER
(FLOOR: 001) LIGHTS NEED SUPPORTS CEILING 410.36
OPEN 07/12/2017 07/12/2017
 
003 (999) OTHER
(FLOOR: 001) HANDLE TIES NEEDED BOTH PANELS 210.4
OPEN 07/12/2017 07/12/2017
 
004 (999) OTHER
(FLOOR: 001) EGC DISHWASHER UNDERSIZED 250.122
OPEN 07/12/2017 07/12/2017



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back