| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
20 |
3C #2 BX. |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER CELLAR #4 AWG CONDUCTOR NOT PROPERLY FUSED AT 100 AMP FOR APT RISERS 240.4 |
OPEN |
10/08/2015 |
10/08/2015 |
|
| |
| 002 |
(999) |
OTHER HALLWAY N FIRE PROOFING PROVIDED, WHER EMT CONDUIT PASSING THROUHGHALLWAY FLOOR. 300.21 |
OPEN |
10/08/2015 |
10/08/2015 |
|
| |
| 003 |
(999) |
OTHER OTHER PANELS IN APT LACKS MECHANICAL CONTINUITY COCENTRIC NO BROKEN309.10 |
OPEN |
10/08/2015 |
10/08/2015 |
|
| |
| 004 |
(999) |
OTHER OTHER NO GROUNDING CONDUCTOR PROVIDED FOR FMC FROM HALLWAY PULL BOXTO PANEL 250.11 |
OPEN |
10/08/2015 |
10/08/2015 |
|
| |
| 005 |
(999) |
OTHER OTHER CONDUCTORS NOT PROPERLY DERATED IN K INCH EMT RISER PIPES 31015B2A |
OPEN |
10/08/2015 |
10/08/2015 |
|
| |
| 006 |
(128) |
NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH (ALL FLOORS) 3 WIRE CORD : IN EL. STOVE NEUTRAL BONDED |
OPEN |
06/17/2016 |
06/17/2016 |
|
| |
| 007 |
( 25) |
ARMORED CABLES ARE NOT PROPERLY TERMINATED (ALL FLOORS) PANEL : MC CABLE GND NOT TERMINATED |
OPEN |
06/17/2016 |
06/17/2016 |
|
| |
| 008 |
( 29) |
OUTLET BOXES ARE NOT COVERED (ALL FLOORS) EL. STOVE BOX MISSING COVER |
OPEN |
06/17/2016 |
06/17/2016 |
|
| |
| 009 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY (ALL FLOORS) NO PANEL DIRECTORY |
OPEN |
06/17/2016 |
06/17/2016 |
|
| |
| 010 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED (ALL FLOORS) PULL BOX TOO SMALL 314.28 |
OPEN |
06/17/2016 |
06/17/2016 |
|