BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M370885
Premises: 171 EAST 79 STREET MANHATTAN BIN: 1047474     Block: 1508   Lot: 27
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 175 E 79 ST Census Tract:   140 Health Area:  3600
APT. 6C Admin Area:   M - MANHATTAN Inspection Area:   J
NEW YORK, NY 10075 Community Board:   108
DOB Cross Street(s):   LEXINGTON AVENUE,    3 AVENUE
Status:   C - JOB IS SIGNED OFF 06/24/2024
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/06/2015 11:49 AM
Application Entered:   08/06/2015 Job Start Date:   08/06/2015
Last Change:   06/24/2024 Job End Date:   04/30/2016
Appointment Status:   
Last Inspection By:   ANGUIANO, VICTOR       On     05/22/2024      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011538 Licensee Name: NICHOLAS BLASONE
Firm: 003044 Firm Name: NEW CENTURY ELEC'L CONTR
Firm Phone: 718-441-7123  Firm Address: 105-15 JAMAICA AVE INC. QUEENS NY 11418 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $43.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: KEVIN FLACK
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
006  6C  10               
Buildings Total 10                  
Total Units : 25 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 03/30/2024
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M370885
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/16/2016 05/17/2016 PHG V (35) (2)
INSPECTION COMMENTS: CONTRACTOR NOT PRESENT FUL INSPECT NEEDED
 
(2) 03/29/2024 03/30/2024 GGC V Y (43) (6)
INSPECTION COMMENTS: FAIL. INSPECTION COMPLETE. OBJECTIONS ISSUED. ATOI: NICK
 
(3) 05/15/2024 05/16/2024 MJK N (22) (0) Y
INSPECTION COMMENTS: NO ACCESS. NO SHOW. TRIED TO GAIN ACCESS FOR VISUAL INSPECTION, ACCESS NOT PROVIDED. NOTIFIED OFFICE, OK TO PROCEED AS PER DIRECTED BY OFFICE ASK.
 
(4) 05/22/2024 05/23/2024 VGV C R (40) (0)
INSPECTION COMMENTS: OBJECTIONS CORRECTED, COMPLETE BY PREVIOUS INSPECTOR. ATOI NICHOLAS

OBJECTION FOR APPLICATION #: M370885
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(FLOOR: 006) BURIED BOX FOR PANEL FEED AND BRANCH 314.29
RSLV 05/16/2016 05/16/2016 03/29/2024
 
002 (999) OTHER
(FLOOR: 006) NO HANDLE TIES FOR MULTI WIRE CKT 210.4
RSLV 05/16/2016 05/16/2016 05/22/2024
 
003 (132) EQUIPMENT/MATERIAL IS NOT PROPERLY GROUNDED
(FLOOR: 006)SELF TOP SCREW USED FOR GROUND TAILS IN KITCHEN RECEPTACLES250.8(A) PROVIDE BEFORE AND AFTER PHOTO FOR THIS OBJECTION (TUR)NOTE ADDED IN FINALIZATION.
RSLV 03/29/2024 03/29/2024 05/22/2024
 
004 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(FLOOR: 006)15A PROVIDED FOR KITCHEN SMALL APPLIANCE BRANCH CIRCUITS 210.11PROVIDE BEFORE AND AFTER PHOTO FOR THIS OBJECTION (TUR) NOTE ADDEDIN FINALIZATION.
RSLV 03/29/2024 03/29/2024 05/22/2024
 
005 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(FLOOR: 006)MULTI WIRE BRANCH CIRCUITS NOT PROVIDED WITH HANDLE TIES 210.4PROVIDE BEFORE AND AFTER PHOTO FOR THIS OBJECTION (TUR) NOTE ADDEDIN FINALIZATION.
RSLV 03/29/2024 03/29/2024 05/22/2024
 
006 (176) INSTALLATION DOES NOT MEET CODE REQUIREMENTS
(FLOOR: 006) RECEPTACLES INSTALLED ON WALLS NOT TR TYPE406.11PROVIDE BEFORE AND AFTER PHOTO FOR THIS OBJECTION (TUR) NOTE ADDEDIN FINALIZATION.
RSLV 03/29/2024 03/29/2024 05/22/2024
 
007 (312) AC OUTLET NOT PROVIDED
(FLOOR: 006)DEDICATED OUTLET FOR WINDOW A/C UNIT IN BEDROOM NOT PROVIDED 210.52PROVIDE BEFORE AND AFTER PHOTO FOR THIS OBJECTION (TUR) NOTE ADDEDIN FINALIZATION.
RSLV 03/29/2024 03/29/2024 05/22/2024
 
008 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(FLOOR: 006) PANEL DIRECTORY NOT ACCURATE 408.4PROVIDE BEFORE AND AFTER PHOTO FOR THIS OBJECTION (TUR) NOTE ADDEDIN FINALIZATION.
RSLV 03/29/2024 03/29/2024 05/22/2024



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order