Electrical Application Details for App #: M370865
Premises: 40 PECK SLIP MANHATTAN BIN: 1001338     Block: 97   Lot: 31
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 40 PECK SLIP Census Tract:   15.01 Health Area:  7700
FLOORS 1-5, & ROOF Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10038 Community Board:   101
Special Place Name:   SUPERIOR OFFICERS COUNCIL
DOB Cross Street(s):   FRONT STREET,    SOUTH STREET
Status:   C - JOB IS SIGNED OFF 04/27/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/06/2015 8:21 AM
Application Entered:   08/06/2015 Job Start Date:   08/06/2015
Last Change:   04/27/2018 Job End Date:   03/25/2016
Appointment Status:   
Last Inspection By:   RACEWICZ, TOMASZ       On     03/16/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011850 Licensee Name: JAMES P ST. JOHN
Firm: 003455 Firm Name: PATRIOT ELECTRIC CORP
Firm Phone: 718-736-8733  Firm Address: 15-17 126TH STREET 3RD FLOOR COLLEGE POINT NY 11356 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $501.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: TED O'ROURKE
Owner Business Name: ICS BUILDERS, INC.
Authorized Representative:  TED O'ROURKE
Relationship To Owner:   OWNER'S REP


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  4 #500 MCM
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  4- # 500MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  4- #1/0, 4-#2
D. 3 Phase Over 225 AMPS  1  4- #500MCM
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001      32    19  33         
002      34    24  30         
003      24    18  33         
004      31    38         
005      17    41         
ROF        12             
Buildings Total   141    77  187          32      
Total Units : 437 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: C - CALL TO OFFICE 03/28/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  GENERAL LIGHTING, RECEPTACLES, HVAC, PANELS

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M370865
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/28/2016 09/29/2016 MQY V (135) (4)
INSPECTION COMMENTS: NO ACCESS TO GEC OR SUPPLEMENTAL, CHECK GROUNDING AND BONDING
 
(2) 12/01/2016 12/05/2016 PHG V Y (35) (2)
INSPECTION COMMENTS: CONTRACTOR TO FILE FOR A/C WORK AND MOTORS. DID NOT INSPECT BRANCH CKTS. ROOF SERVICE ROOM ONLY .
 
(3) 03/28/2017 03/28/2017 CBK J X (50) (0) Y
INSPECTION COMMENTS: OBJECTIONS NOT REMOVED.
 
(4) 03/01/2018 03/02/2018 TOR J Y (40) (0)
INSPECTION COMMENTS: FAIL.
 
(5) 03/16/2018 03/19/2018 TOR C R (30) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: M370865
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ROOF) SERVICE RACEWAY NOT BONDED SMALLER THAN NEC 250.66 (250.80)
RSLV 09/28/2016 09/28/2016 03/16/2018
 
002 (999) OTHER
(ROOF) MAIN BONDING JUMPER MISSING FROM SS (250.92)(250.24)
RSLV 09/28/2016 09/28/2016 03/16/2018
 
003 (999) OTHER
(ROOF) NEUTRAL BONDED IN PANEL AFTER SS (250.24A5)
RSLV 09/28/2016 09/28/2016 12/01/2016
 
004 (999) OTHER
(ROOF)UTILITY MAN HOLE IS NOT ACCESSIBLE, BOTTOM STAIR IS BUILD ON MANHOLE COVER (110.73)
RSLV 09/28/2016 09/28/2016 03/01/2018
 
005 ( 53) GFCI HAS NOT BEEN PROVIDED
(FLOOR: 001) NO GFCI PROVIDED NEXT TO PANTRY WATER FOUNTAIN 210.8
RSLV 12/01/2016 12/01/2016 03/01/2018
 
006 (136) GROUNDING ELECTRODE CONDUCTOR IS NOT CONTINUOUS
(ROOF) NO METAL CONTACT FOR GEC PIPE IN TROUGH ON ROOF
RSLV 12/01/2016 12/01/2016 03/01/2018