BIS Menu  |  Elevators  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M370741
Premises: 106 HUDSON STREET MANHATTAN BIN: 1066469     Block: 189   Lot: 7502
   
Application Completed and Certified

Filed: 110 HUDSON ST Census Tract:   33 Health Area:  7700
FLOORS 1 - 10 Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10013 Community Board:   101
DOB Cross Street(s):   FRANKLIN STREET,    NORTH MOORE STREET
Status:   C - JOB IS SIGNED OFF 10/01/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/03/2015 9:05 PM
Application Entered:   08/03/2015 Job Start Date:   08/04/2015
Last Change:   10/01/2015 Job End Date:   10/01/2015
Appointment Status:   
Last Inspection By:   ERIC HIRSCH       On     09/16/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010766 Licensee Name: JOHN E CUTRUPI
Firm: 002008 Firm Name: PREFERRED ELECT'L CONTR'G
Firm Phone: 718-967-0032  Firm Address: 1442 86TH STREET BROOKLYN NY 11228 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $415.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: CHUCK LOWE
Owner Business Name: BORDEN HOUSE CONDOMINIUM
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  #4
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  4  100 AMP
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  6  125 AMP
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 09/02/2015
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  REPLACE HOUSE PANELS IN HALLWAYS

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M370741
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/25/2015 09/02/2015 BUR A (50) (3) Y
INSPECTION COMMENTS: NONE
 
(2) 09/16/2015 09/22/2015 ECH C R (70) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M370741
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
8TH AND 9TH FLOOR: BREAKER BEING BACK FED NOT SECURED 408.36D
RSLV 08/25/2015 08/25/2015 09/16/2015
 
002 (999) OTHER
8TH,5TH, 4TH, 3RD, 2ND 1ST FLOOR MULTI-WIRE HAS NO SIMULTANEOUSTLYDISCONNECT MEANS 210.4
RSLV 08/25/2015 08/25/2015 09/16/2015
 
003 (999) OTHER
6TH, 5TH ANF 1ST FLOOR NOT PROPERLY TAP 240.21
RSLV 08/25/2015 08/25/2015 09/16/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Elevators  |  Electrical Inspection Work Order  |  Back