BIS Menu  |  Property Profile  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M370704
Premises: 240 PARK AVENUE MANHATTAN BIN: 1035405     Block: 1282   Lot: 34
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 250 PARK AV Census Tract:   94 Health Area:  4800
3/5 Admin Area:   M - MANHATTAN Inspection Area:   L
NEW YORK, NY 10017 Community Board:   105
Special Place Name:   ARTHUR GALLAGHER
DOB Cross Street(s):   EAST 46 STREET,    EAST 47 STREET
Status:   C - JOB IS SIGNED OFF 12/30/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/03/2015 10:26 AM
Application Entered:   08/03/2015 Job Start Date:   08/03/2015
Last Change:   12/30/2015 Job End Date:   08/03/2016
Appointment Status:   
Last Inspection By:   RAMJAG, BUDRAM       On     12/23/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010763 Licensee Name: STEPHEN ROSTOWSKY
Firm: 002342 Firm Name: ROCKMOR ELEC. ENTERPR INC
Firm Phone: 718-633-3700  Firm Address: 1042 39TH STREET BROOKLYN NY 11219 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $308.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: NUCOR CONSTRUCTION CORP
Authorized Representative:  SPENCER BALDWIN
Relationship To Owner:   PROJECT MANAGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  2  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  2  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
003    28  10    28             
005    179  102    33  179             
Buildings Total 207  112    36  207                
Total Units : 562 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 11/25/2015
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  JOB #50633 02461-000

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M370704
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/20/2015 11/25/2015 PHG A (40) (4) Y
INSPECTION COMMENTS: NONE
 
(2) 12/23/2015 12/28/2015 BUR C R (45) (0)
INSPECTION COMMENTS: OBJECTIONS REMOVED

OBJECTION FOR APPLICATION #: M370704
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(ALL FLOORS) 5FL #4 ON 100AMP BREAKER 240.3
RSLV 11/20/2015 11/20/2015 12/23/2015
 
002 (999) OTHER
(ALL FLOORS) 5FL: 17 #10 WIRES IN 7" PIPE
RSLV 11/20/2015 11/20/2015 12/23/2015
 
003 ( 53) GFCI HAS NOT BEEN PROVIDED
(ALL FLOORS) 5FL NO GFC 6FL FROM SINK SMALL PANTRY 210.8
RSLV 11/20/2015 11/20/2015 12/23/2015
 
004 (999) OTHER
(ALL FLOORS) 3FL NO HANDLE TIES FOR 3FL PANNEL 210.4
RSLV 11/20/2015 11/20/2015 12/23/2015