Electrical Application Details for App #: M370659
Premises: 65 EAST 12 STREET MANHATTAN BIN: 1009212     Block: 564   Lot: 54
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 77 E 12 ST Census Tract:   61 Health Area:  5700
BASEMENT Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10003 Community Board:   102
DOB Cross Street(s):   BROADWAY,    4 AVENUE
Status:   C - JOB IS SIGNED OFF 04/05/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/31/2015 3:14 PM
Application Entered:   07/31/2015 Job Start Date:   08/03/2015
Last Change:   04/05/2018 Job End Date:   11/30/2015
Appointment Status:   
Last Inspection By:   VINCENT CASTALDO       On     04/05/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010152 Licensee Name: JAMES TIZIO
Firm: 000339 Firm Name: COMMUNITY ELEC., INC.
Firm Phone: 718-720-4188  Firm Address: 124 GRANITE AVENUE STATEN ISLAND NY 10303 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
9 - OTHER
Total Fee:  $52.75
Other Work:   INSTALL GENERATOR
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JAMES FREIBAND
Owner Business Name: DOUGLAS ELLIMAN PROPERTY
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS            60         
Buildings Total            60           
Total Units : 61 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: C - CALL TO OFFICE 09/07/2017
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M370659
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/03/2016 11/04/2016 MLF V (30) (1)
INSPECTION COMMENTS: OBJECTION ISSUED
 
(2) 01/23/2017 01/24/2017 JTE V R (25) (2)
INSPECTION COMMENTS: INSPECTION FAILED, SEE OBJECTION DEATILS.
 
(3) 03/31/2017 04/03/2017 EDB V X (80) (2)
INSPECTION COMMENTS: SEE ATTACHMENT.
 
(4) 09/06/2017 09/07/2017 EDB H X (50) (0) Y
INSPECTION COMMENTS: SEE ATTACHMENT.
 
(5) 04/05/2018 04/05/2018 VTC C R (27) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: M370659
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (127) NO GROUND HAS BEEN PROVIDED FOR SEPARATELY DERIVED SYSTEM
(BASEMENT) CO GEN 65 KW GEN NOT GROUNDED
RSLV 11/03/2016 11/03/2016 01/23/2017
 
002 (127) NO GROUND HAS BEEN PROVIDED FOR SEPARATELY DERIVED SYSTEM
(BASEMENT) EGC FROM GENERATOR TO BUILDING STEEL REQUIRES A PERMANENTCONNECTION.
RSLV 01/23/2017 01/23/2017 04/05/2018
 
003 (136) GROUNDING ELECTRODE CONDUCTOR IS NOT CONTINUOUS
(BASEMENT)RACEWAY TO GENERATO RQUIRES GROUNG TO BE CONTINUES THROUGH SYSTEM.
RSLV 01/23/2017 01/23/2017 04/05/2018
 
004 (109) SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED
(CELLAR)NO WORKING SPACE IN FRONT OF MAIN GENERATOR SW. 110.26
RSLV 03/31/2017 03/31/2017 04/05/2018
 
005 ( 19) DEFECTIVE WIRING IS IN USE
(CELLAR) 3/0 AWG ON 250 A CB T. 310.16
RSLV 03/31/2017 03/31/2017 04/05/2018