BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M370377
Premises: 252 ELIZABETH STREET MANHATTAN BIN: 1007855     Block: 507   Lot: 14
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 252 ELIZABETH ST Census Tract:   43 Health Area:  6800
BASEMENT & APT #1 Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10012 Community Board:   102
DOB Cross Street(s):   PRINCE STREET,    EAST HOUSTON STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/24/2015 11:10 AM
Application Entered:   07/24/2015 Job Start Date:   07/24/2015
Last Change:   08/22/2025 Job End Date:   02/15/2016
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   PANAYOTEDIS, STEPHEN       On     06/30/2016      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  
Objection Disposition:  

License #: 010981 Licensee Name: VASILIOS BILLY TAKOS
Firm: 001408 Firm Name: TAKOS AND K ELECTRIC INC
Firm Phone: 718-472-1300  Firm Address: 38-58 11TH STREET LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $235.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (2  Stores, 8 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ROBERT GORDON
Owner Business Name: AJ CLARKE
Authorized Representative:  ROBERT GORDON
Relationship To Owner:   MANAGER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  2  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  2  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  2  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 10 #4-Wire 1 #10-Wire 0
Existing Meters 11 + New Meters 10 - Removed Meters 10 = Total Meters 11

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 07/24/2015 Notice: 1 - FIRST NOTICE 07/01/2016
Power Issued: 07/24/2015 Response:  

Follow-Up:
Contractor's Comments:  REPLACING ALL EXISTING DEFECTIVE SERVICE AND METER EQUIPMENT FOR APARTMENTS AND COMMERCIAL SPACE N ALL EXISTING SUB-FEEDERS FOR APARTMENTS & COMMERCIAL SPACE N (WITH THE EXCEPTION OF APT #1&COMMERCIAL SPACE S ) TO REMAIN AND BE REUSED INSTALLING NEW SUB-FEEDER AND PANEL FOR APARTMENT #1. REROUTI

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M370377
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/30/2016 07/01/2016 STP V (45) (4)
INSPECTION COMMENTS: FAIL. CONTRACTOR SAID HE DID NOT DO NO BRANCH CKT WIRING IN COMMERCIAL SPACE OR APARTMENT. JUST DID SERVICE STUFF AND RISERS

OBJECTION FOR APPLICATION #: M370377
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(BASEMENT) NO CONTINUITY OF PIPE TO CON ED BOX. 300.10
OPEN 06/30/2016 06/30/2016
 
002 (999) OTHER
(BASEMENT) DOUBLE LUGGING ON POLARIS TAP CON ED BOX 110.14
OPEN 06/30/2016 06/30/2016
 
003 (999) OTHER
(BASEMENT) SERVICE ENTRANCE EXTENDED INTO TROUGH LOCAL LAW 230.46
OPEN 06/30/2016 06/30/2016
 
004 (999) OTHER
(GROUND FLOOR) PANEL IN COMMERCIAL SPACE NEUTRAL BONDED 250.24
OPEN 06/30/2016 06/30/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.