| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(111) |
SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED (FLOOR: 006) NO WORKING SPACE PANEL IN CLOTHES CLOSET 110.26 |
OPEN |
09/12/2018 |
09/12/2018 |
|
| |
| 002 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED (FLOOR: 006) HANGING LIVING ROOM LIGHT NO GROUND 250.122 |
OPEN |
09/12/2018 |
09/12/2018 |
|
| |
| 003 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED (FLOOR: 007) PULL BOX 7 A MC CABLE NOT TERMINATED 250.8 |
OPEN |
09/12/2018 |
09/12/2018 |
|
| |
| 004 |
( 16) |
DEFECTIVE LIGHTING FIXTURES ARE IN USE (FLOOR: 008) EXPOSED BULB IN CLOTHES CLOSET 8 FL 410.16 |
OPEN |
09/12/2018 |
09/12/2018 |
|
| |
| 005 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED (FLOOR: 009) MC CABLE NOT TERMINATED APT 9 D |
OPEN |
09/12/2018 |
09/12/2018 |
|
| |
| 006 |
(229) |
SPLICE BOXES NOT ACCESSIBLE (FLOOR: 009) BURIED BOX APT 9 A 314.29 |
OPEN |
09/12/2018 |
09/12/2018 |
|
| |
| 007 |
(283) |
SMALL APPLIANCE OUTLETS NOT PROPERLY LOCATED (FLOOR: 011) IMPROPER KITCHEN PLACEMENT 11 FL 210.52 |
OPEN |
09/12/2018 |
09/12/2018 |
|
| |
| 008 |
( 63) |
RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER (FLOOR: 011) NO OUTLET FOR ALL BALCONY 11 FL 210.63 |
OPEN |
09/12/2018 |
09/12/2018 |
|
| |
| 009 |
(128) |
NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH (ALL FLOORS) ALL PANELS NEUTRAL BONDED 250.24 |
OPEN |
09/12/2018 |
09/12/2018 |
|
| |
| 010 |
(229) |
SPLICE BOXES NOT ACCESSIBLE (ALL FLOORS) ALL D LINE BURIED BOX NEXT TO CA 314.29 |
OPEN |
09/12/2018 |
09/12/2018 |
|
| |
| 011 |
( 29) |
OUTLET BOXES ARE NOT COVERED (ALL FLOORS) ALL AIR HANDIER DISCONNECT NOT COVERED |
OPEN |
09/12/2018 |
09/12/2018 |
|
| |
| 012 |
(296) |
PANEL IS LOCATED IN CLOTHES/LINEN CLOSET (ALL FLOORS) ALL D LINE PANEL IN CLOTHES CLOSET 240.24 |
OPEN |
09/12/2018 |
09/12/2018 |
|
| |
| 013 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED (ALL FLOORS) NO AFCI ON ALL 120 V LAUNDRY CKT 210.12 |
OPEN |
09/12/2018 |
09/12/2018 |
|
| |
| 014 |
(111) |
SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED (ROOF) NO WORKING SPACE FOR ALL AC DISCONNECTS |
OPEN |
09/12/2018 |
09/12/2018 |
|
| |
| 015 |
( 14) |
CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE (ROOF) AC FOR APT 4C OVER FUSED 240.4 |
OPEN |
09/12/2018 |
09/12/2018 |
|
| |
| 016 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED (ROOF) GROUNDS NOT TERMINATED ROOF PANEL 250.8 |
OPEN |
09/12/2018 |
09/12/2018 |
|
| |
| 017 |
( 63) |
RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER (ROOF) NO OUTLETS 25 FT FROM UNIT BOTH LEVELS OF ROOF 210.63 |
OPEN |
09/12/2018 |
09/12/2018 |
|
| |
| 018 |
(999) |
OTHER (ROOF) NO HANDLE TIES ROOF PANEL 210.4 |
OPEN |
09/12/2018 |
09/12/2018 |
|