Electrical Application Details for App #: M369248
Premises: 11 WEST 12 STREET MANHATTAN BIN: 1009621     Block: 576   Lot: 48
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 11 W 12 ST Census Tract:   63 Health Area:  5700
1-7 Admin Area:   M - MANHATTAN Inspection Area:   S
NEW YORK, NY 10011 Community Board:   102
DOB Cross Street(s):    5 AVENUE,    AVENUE OF THE AMERICAS
Status:   C - JOB IS SIGNED OFF 05/16/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/25/2015 12:47 PM
Application Entered:   06/25/2015 Job Start Date:   06/26/2015
Last Change:   05/16/2018 Job End Date:   08/10/2015
Appointment Status:   
Last Inspection By:   GANITIS, PHILLIP       On     05/16/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010520 Licensee Name: MILAN BONETA
Firm: 001695 Firm Name: FINA ELEC'L CONTRS. INC.
Firm Phone: 718-278-9431  Firm Address: 18-65 42 STREE LONG ISLAND CITY NY 11105 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $165.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   A - One Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: TERRENCE LOWENBERG
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  1  CONTROL WIRING
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 04/18/2018
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  CONTROL WIRING FOR 7 STOP ELEVATOR.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M369248
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/18/2018 04/18/2018 STP V (35) (4)
INSPECTION COMMENTS: FAIL. OBJECTIONS ISSUED.
 
(2) 05/16/2018 05/16/2018 PHG C R (30) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: M369248
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(BASEMENT) WORK SPACE FOR BOTH DISCONNECT SWITCHS 110.26
RSLV 04/18/2018 04/18/2018 05/16/2018
 
002 (999) OTHER
(BASEMENT) UL LISTING FOR MOTOR IN OIL 110.3
RSLV 04/18/2018 04/18/2018 05/16/2018
 
003 (999) OTHER
(BASEMENT) SIZE FUSES FOR MOTOR IN USE 430.52
RSLV 04/18/2018 04/18/2018 05/16/2018
 
004 (999) OTHER
(BASEMENT) MAIN LINE WIRE UNDERSIZED FOR MOTOR 430.6
RSLV 04/18/2018 04/18/2018 05/16/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back