BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M368914
Premises: 109 NASSAU STREET MANHATTAN BIN: 1089790     Block: 90   Lot: 17
   
Application Completed and Certified

Filed: 113 NASSAU ST Census Tract:   15.01 Health Area:  7700
GROUND Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10038 Community Board:   101
DOB Cross Street(s):   ANN STREET,    BEEKMAN STREET
Status:   C - JOB IS SIGNED OFF 09/16/2015
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/17/2015 11:06 PM
Application Entered:   06/17/2015 Job Start Date:   06/17/2015
Last Change:   09/16/2015 Job End Date:   11/17/2015
Appointment Status:   
Last Inspection By:   BERGMAN EDUARD       On     08/13/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  G - NO COMMENT
Objection Disposition:  R - REMOVED

License #: 011577 Licensee Name: CHRIS J RAGAVANIS
Firm: 003217 Firm Name: CHT ELECTRIC CORP.
Firm Phone: 347-201-1941  Firm Address: 116 NASSAU STREET NEW YORK NY 10038 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $878.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   BLINK FITNESS
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: CHAMBERS ROMERO
Owner Business Name: ECLIPSE DEVELOPMENT
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  2  
B. Over #2 to 1/0  2  
C. Over 1/0 to 250 MCM  2  
D. Over 250 MCM  2  500MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  6  200A
D. 3 Phase Over 225 AMPS  1  800A
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND    105  200    20  200  20         
Buildings Total 105  200    20  200     20           
Total Units : 545 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 06/17/2015 Notice: 1 - FIRST NOTICE 07/08/2015
Power Issued: 06/17/2015 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  #51084 - THIS PERMIT REPLACES PERMIT #M359074

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M368914
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/30/2015 07/08/2015 EDB A E (90) (5) Y
INSPECTION COMMENTS: NONE
 
(2) 08/03/2015 08/12/2015 EDB Z (0) (0) Y
INSPECTION COMMENTS: CANCEL WITH OFFICE
 
(3) 08/13/2015 08/18/2015 EDB C R G (85) (0) Y
INSPECTION COMMENTS: NONE

OBJECTION FOR APPLICATION #: M368914
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
T-OUT: DEVICE BOX(S) TOO SMALL T 314.16A
RSLV 06/30/2015 06/30/2015 08/13/2015
 
002 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
ELEV. RM.: STRAIT PULL BOX FOR 2X 500MCM TOO SMALL 314.28
RSLV 06/30/2015 06/30/2015 08/13/2015
 
003 (999) OTHER
2,3FL NO FIRE STOP IN EL. RM 300.21
RSLV 06/30/2015 06/30/2015 08/13/2015
 
004 ( 21) CONDUCTORS HAVE NOT BEEN PROPERLY DE-RATED
2,3FL: EL RM THROUGH HAS OVER 30 CURRENT CONDUCTORS 376.22
RSLV 06/30/2015 06/30/2015 08/13/2015
 
005 (999) OTHER
T-OUT: EXIT LIGHT FIXTURE SUPPORT W/ EMT 358.12(5)
RSLV 06/30/2015 06/30/2015 08/13/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back