BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M368896
Premises: 273 BROADWAY MANHATTAN BIN: 1001635     Block: 149   Lot: 33
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 277 BROADWAY Census Tract:   21 Health Area:  7700
SUB CELLAR Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10007 Community Board:   101
DOB Cross Street(s):   CHAMBERS STREET,    READE STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/17/2015 3:02 PM
Application Entered:   06/17/2015 Job Start Date:   06/17/2015
Last Change:   08/22/2025 Job End Date:   06/16/2016
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   WEISBART, F.       On     11/14/2015      
Field Disp:   J - JOB IN PROGRESS
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  Y - PARTLY REMOVED

License #: 010069 Licensee Name: PETER AMABILE
Firm: 003346 Firm Name: FLEMINGTON ELEC'L MAINT I
Firm Phone: 646-230-9903  Firm Address: 225 31 STREET BROOKLYN NY 11232 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $180.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: EDWARDS WILLIAMS
Owner Business Name: AT&T
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  2  SET OF # 3/0
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  42 CIRCUIT PANEL
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 0 + New Meters 1 - Removed Meters 0 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 06/17/2015 Notice: 1 - FIRST NOTICE 08/13/2015
Power Issued: 06/17/2015 Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M368896
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/06/2015 08/13/2015 EDB V D (50) (8) Y
INSPECTION COMMENTS: BUILDING USED RESTED 2000A S.SW
 
(2) 11/14/2015 12/01/2015 FWE J Y E (45) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: M368896
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (121) MORE THAN 6 DISCONNECTS
CELLAR OVER 6 DISC. SM IN SERVICE ROOM. 230.41A
RSLV 08/06/2015 08/06/2015 11/14/2015
 
002 (999) OTHER
CELLAR NO LIGHT ON FRONT OF PANEL 110.26D
OPEN 08/06/2015 11/14/2015
 
003 (109) SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED
CELLAR NO WORKING SPACE FOR NEW 2ND SW. 110.26
OPEN 08/06/2015 11/14/2015
 
004 (124) TAP CONDUCTORS ARE NOT WITHIN 10 FT OR WITHIN 25 FT AS PER CODE
CELLAR TAP FOR NEW SW, OVER 101 240.21
OPEN 08/06/2015 11/14/2015
 
005 (999) OTHER
CELLAR NO ARE FLASH WARNING FOR NEW EQUIPMENT 110.26
OPEN 08/06/2015 11/14/2015
 
006 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
CELLAR NO DIRECTORY FOR NEW PANEL (AT&T) 408.4
OPEN 08/06/2015 11/14/2015
 
007 (255) NO FUSE COORDINATION EXISTS
CELLAR NO FUSE COORDINATION AM 240.12A
OPEN 08/06/2015 11/14/2015
 
008 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
CELLAR MODERNIZATION OF EXISTING 2000 A SERV. DISC SW AM 110.2A
OPEN 08/06/2015 11/14/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order