Electrical Application Details for App #: M368822
Premises: 225 WEST 24 STREET MANHATTAN BIN: 1014174     Block: 774   Lot: 19
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 225 W 24 ST Census Tract:   91 Health Area:  5200
BASEMENT,1,2,3,4,5,6,7,8,9,10 Admin Area:   M - MANHATTAN Inspection Area:   P
NEW YORK, NY 10011 Community Board:   104
Special Place Name:   FASHION HS
DOB Cross Street(s):    7 AVENUE,    8 AVENUE
Status:   C - JOB IS SIGNED OFF 02/16/2017
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/16/2015 1:24 PM
Application Entered:   06/16/2015 Job Start Date:   06/25/2015
Last Change:   02/16/2017 Job End Date:   12/15/2016
Appointment Status:   
Last Inspection By:   TREJO, JORGE       On     02/16/2017      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011754 Licensee Name: PRAKASH KAPADIA
Firm: 002230 Firm Name: KANTA ELECTRIC CORP.
Firm Phone: 718-397-9527  Firm Address: 34-21 56TH ST WOODSIDE NY 11377 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $51.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   W - School
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JEAN CLERIE
Owner Business Name: NYCSCA
Authorized Representative:  JEAN CLERIE
Relationship To Owner:   PROJECT OFFICER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  FIRE ALARM FUSE CUTOUT
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS                       
001                       
002                       
003                       
004                       
005                       
006                       
007                       
008                       
009                       
010                       
Buildings Total   25                      
Total Units : 25 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 10/18/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M368822
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/07/2016 01/07/2016 UMS N (25) (0) Y
INSPECTION COMMENTS: CONTRACTOR NO SHOW, NO ANSWER
 
(2) 10/17/2016 10/18/2016 EDB V (55) (3)
INSPECTION COMMENTS: CONTRACTOR FILED INCORRECTLY ( NO SERVICE WORK/NOTIFIED UTILITY ). INSPECT S. SW. ,GYM AND PANEL.
 
(3) 02/16/2017 02/16/2017 JTE C R (35) (0)
INSPECTION COMMENTS: INSPECTION PASSED, OBJECTIONS REMOVED.

OBJECTION FOR APPLICATION #: M368822
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
(ALL FLOORS) PANELS: ZIP SCREW USED FOR GND 250.8
RSLV 10/17/2016 10/17/2016 02/16/2017
 
002 (133) NO GROUND ROD: BASEMENT OR OUTSIDE
(CELLAR) NO GND ROD 250.50,52...
RSLV 10/17/2016 10/17/2016 02/16/2017
 
003 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
(CELLAR) GEC RUN W/BRANCH CKT. 250
RSLV 10/17/2016 10/17/2016 02/16/2017