BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M368612
Premises: 60 EAST 88 STREET MANHATTAN BIN: 1046927     Block: 1499   Lot: 7501
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 62 E 88 ST Census Tract:   150.02 Health Area:  3600
LOWER LEVEL SUITE B Admin Area:   M - MANHATTAN Inspection Area:   J
NEW YORK, NY 10128 Community Board:   108
DOB Cross Street(s):   MADISON AVENUE,    PARK AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/10/2015 3:30 PM
Application Entered:   06/10/2015 Job Start Date:   06/11/2015
Last Change:   08/22/2025 Job End Date:   06/11/2016
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   PANAYOTEDIS, STEPHEN       On     04/30/2021      
Field Disp:   N - NO ACCESS
Energize Recommendation:  
Objection Disposition:  Y - PARTLY REMOVED

License #: 012593 Licensee Name: FARID J MARJI
Firm: 004424 Firm Name: NEW YORK EMPIRE ELECL CON
Firm Phone: 718-619-8181  Firm Address: 1236 JEROME AVENUE SERVICES INC BRONX NY 10452 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $63.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:   E - EMERGENCY LIGHTING LOCAL LAW 16/84
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MIKE COLAROSSI
Owner Business Name: SIMONE DEVELOPMENT
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS  BAS    40    17  46             
Buildings Total   40    17  46                
Total Units : 103 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 04/10/2019
Power Issued: Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M368612
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/03/2019 01/03/2019 MLF N (10) (0) Y
INSPECTION COMMENTS: NO SHOW
 
(2) 04/10/2019 04/10/2019 DNM V (60) (5)
INSPECTION COMMENTS: OBJECTIONS ISSUED.
 
(3) 12/12/2019 12/12/2019 ASK J Y (15) (0)
INSPECTION COMMENTS: FAIL. JOB IN PROGRESS. OBJECTIONS STILL EXIST.
 
(4) 04/30/2021 05/03/2021 STP N (30) (0) Y
INSPECTION COMMENTS: FAIL. NO ACCESS TO TENANT SPACE. INSPECTION INCOMPLETE.

OBJECTION FOR APPLICATION #: M368612
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
(BASEMENT) KNOCKOUTS MISSING IN X RAY DISCONNECT.
RSLV 04/10/2019 04/10/2019 12/12/2019
 
002 ( 4) SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL
(BASEMENT)SERVICE IS EXCESS OF 1000 KVA HAS NOT BEEN SUBMITTED FOR APPROVAL.
OPEN 04/10/2019 04/10/2019
 
003 (999) OTHER
(BASEMENT) HOSPITAL GRADE CABLE IS REQUIRED 517.13
RSLV 04/10/2019 04/10/2019 12/12/2019
 
004 (999) OTHER
(BASEMENT)ELECTRICIAN RE-INDENTIFIED NEUTRAL AS PHASE IN X RAY DISCONNECT.
OPEN 04/10/2019 04/10/2019
 
005 (999) OTHER
(BASEMENT) ELECTRICIAN MUST FILE PAA FOR NEW FEEDERS, PANEL.
OPEN 04/10/2019 04/10/2019



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.