| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(169) |
TEMPORARY CONSTRUCTION WIRING IS NOT REMOVED (FLOOR: 018) T-OUT |
RSLV |
05/08/2017 |
05/08/2017 |
03/15/2018 |
| |
| 002 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY (FLOOR: 018) NOT REFLECTING FIELD CONDITION AS WELL ON 17 FL |
RSLV |
05/08/2017 |
05/08/2017 |
07/02/2019 |
| |
| 003 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED (FLOOR: 018) AS NEEDED 17 FL INCLUDED |
RSLV |
05/08/2017 |
05/08/2017 |
01/02/2019 |
| |
| 004 |
(999) |
OTHER (FLOOR: 018) MC NOT GROUNDED T-OUT AS WELL 17 FL 250.122 ,250.118 |
RSLV |
05/08/2017 |
05/08/2017 |
01/02/2019 |
| |
| 005 |
(999) |
OTHER (FLOOR: 018) NO HANDLE TIES T-OUT AS WELL 17 FL 210.4B |
RSLV |
05/08/2017 |
05/08/2017 |
03/15/2018 |
| |
| 006 |
(999) |
OTHER (FLOOR: 018)2 MINIMUM CIRCUITS ON COUNTER NOT PROVIDED KITCHEN AREA AS WELL ON17 FL 210.11 |
RSLV |
05/08/2017 |
05/08/2017 |
01/02/2019 |
| |
| 007 |
(999) |
OTHER (FLOOR: 018)NO WR RECEPTACLE PROVIDED T-OUT AS WELL 17 FL (ALL BALCONY AREA)406.8 |
RSLV |
05/08/2017 |
05/08/2017 |
03/15/2018 |
| |
| 008 |
(110) |
SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED (FLOOR: 013) MDP 13 FL BATHROOM NO WORKING SPACE FOR MDP |
RSLV |
07/14/2017 |
07/14/2017 |
07/02/2019 |
| |
| 009 |
( 14) |
CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE (ALL FLOORS) AIR HANDLERS OVER FUSED T OUT |
RSLV |
07/14/2017 |
07/14/2017 |
03/15/2018 |
| |
| 010 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER (BASEMENT) NO BOND FOR CON ED BOX LOADS |
RSLV |
07/14/2017 |
07/14/2017 |
07/02/2019 |
| |
| 011 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER (BASEMENT) NO BONDING IN PIPES ABOVE CT 250.93 |
RSLV |
07/14/2017 |
07/14/2017 |
07/02/2019 |
| |
| 012 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER (BASEMENT) 2 INCH LINE CON ED BOX AND SERVICE SW 250.93 |
RSLV |
07/14/2017 |
07/14/2017 |
07/02/2019 |
| |
| 013 |
( 14) |
CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE (BASEMENT) FIRE PUMP UNDER FUSED 695..4 |
RSLV |
07/14/2017 |
07/14/2017 |
03/15/2018 |
| |
| 014 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED (BASEMENT) FIRE PUMP GEC UNDER SIZED 250.122 |
RSLV |
07/14/2017 |
07/14/2017 |
07/02/2019 |
| |
| 015 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT) NO GROUPING IN TROUGH AS PER PRINT |
RSLV |
07/14/2017 |
07/14/2017 |
07/02/2019 |
| |
| 016 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT) SERVICE SW 4 CONDUCTORS LOAD NOT AS PER PRINT |
RSLV |
07/14/2017 |
07/14/2017 |
07/02/2019 |
| |
| 017 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT) GENERATOR BREAKER NOT AS PER PRINT |
RSLV |
07/14/2017 |
07/14/2017 |
07/02/2019 |
| |
| 018 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT) NO PUSH BAR IN SERVICE RM 110.26 |
RSLV |
07/14/2017 |
07/14/2017 |
07/02/2019 |
| |
| 019 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT) SERVICE ENTRACNCE CON ED FEED NOT AS PER PRINT |
RSLV |
07/14/2017 |
07/14/2017 |
07/02/2019 |
| |
| 020 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT) FUSES DONT MATCH IN SERVICE 2,3 ,4 |
RSLV |
07/14/2017 |
07/14/2017 |
07/02/2019 |
| |
| 021 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT) BREAKERS ADEDED TO MDP RPD2 HDP |
RSLV |
07/14/2017 |
07/14/2017 |
07/02/2019 |
| |
| 022 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT) FIRE ALARM ATS NO AS PER PRINT |
RSLV |
07/14/2017 |
07/14/2017 |
07/02/2019 |
| |
| 023 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT) TAPS NOT IN 10 FT AS PER PRINT |
RSLV |
07/14/2017 |
07/14/2017 |
07/02/2019 |
| |
| 024 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (BASEMENT)200 AMP SERVICE SW GROUNDING NOT AS PER PRINT 250.66 250.53 |
RSLV |
07/14/2017 |
07/14/2017 |
07/02/2019 |
| |
| 025 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY (BASEMENT) NEUTRAL IN GENERATOR NOT BONDED 250.66 |
RSLV |
07/14/2017 |
07/14/2017 |
07/02/2019 |
| |
| 026 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY (BASEMENT)FIRE ALARM FROM GENERATOR NO GEC AND AND BONDING JUMPER 250.8250.66 |
RSLV |
07/14/2017 |
07/14/2017 |
07/02/2019 |
| |
| 027 |
( 9) |
SQ AREA OF SUM OF CONDUCTORS EXCEEDS SQ AREA FILL OF RACEWAY (BASEMENT) MILL CUT FROM LINE OF GENERATOR |
RSLV |
07/14/2017 |
07/14/2017 |
07/02/2019 |
| |
| 028 |
(999) |
OTHER (BASEMENT) NO SUPPLEMENT GROUND FRO ALL SERVICE SW 250.53 |
RSLV |
07/14/2017 |
07/14/2017 |
01/02/2019 |
| |
| 029 |
(999) |
OTHER (BASEMENT) BREAKER IN GENERATOR IS BROKEN 110.3 |
RSLV |
07/14/2017 |
07/14/2017 |
07/02/2019 |
| |
| 030 |
(999) |
OTHER (BASEMENT) NETURAL ON LINE SIDE OF LINK 408.60 |
RSLV |
07/14/2017 |
07/14/2017 |
03/15/2018 |
| |
| 031 |
(999) |
OTHER (BASEMENT) SCREWS NOT TIGHT ON ELD LINE BUS BAR 110.3 |
RSLV |
07/14/2017 |
07/14/2017 |
01/02/2019 |
| |
| 032 |
(999) |
OTHER (BASEMENT) JOCKEY PUMP TAP NOT PERMITED |
RSLV |
07/14/2017 |
07/14/2017 |
03/15/2018 |
| |
| 033 |
(128) |
NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH (FLOOR: 002)250.24 2ND FLOOR MECHANICAL ROOM PANEL NEUTRAL BONDED (ALSO KO SEALSOPEN AND GROUPING MISSING) |
RSLV |
08/12/2017 |
08/12/2017 |
07/02/2019 |
| |
| 034 |
( 18) |
DEFECTIVE RECEPTACLES ARE IN USE (FLOOR: 002)110.2 THERE IS DEFECTIVE OUTLETS IN TOP PENT HOUSE NOT WORKING INLIVING ROOM AND KITCHEN AREAS, |
RSLV |
08/12/2017 |
08/12/2017 |
03/15/2018 |
| |
| 035 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY (FLOOR: 002)408.4 ALL PANELS NEED PROPER AND COMPLETE DIRECTORIES FROM ROOF TOCELLAR |
RSLV |
08/12/2017 |
08/12/2017 |
07/02/2019 |
| |
| 036 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (FLOOR: 002)210.52D IN ALL BATHROOMS WITH DOUBLE SINKS MUST HAVE A GFCI WITHIN3FT OF THE OUTER EDGE OF THE SINK NEED SECOND SINK OUTLET SO WIRINGWILL NOT CROSS SINK ON RIGHT THIS OBJECTION IS FOR ALL UNITS FROMROOF TO THE BASEMENT |
RSLV |
08/12/2017 |
08/12/2017 |
07/02/2019 |
| |
| 037 |
(999) |
OTHER (FLOOR: 002) 110.2 TWO GANG FLOOR OUTLETS NO DIVIDER FOR VOLTAGES |
RSLV |
08/12/2017 |
08/12/2017 |
07/02/2019 |
| |
| 038 |
( 15) |
FLEXIBLE CORDS USED AS PERMANENT WIRING METHOD (FLOOR: 013)400.8 THREE PENDANT LIGHTS OVER TABLE IN AMENITIES AREA NOTINSTALLED IN A APPROVED MANNER FLEXIBLE WIRING CANNOT BE INSTALLEDIN THE CEILING PLENUM AND BOX MUST BE PROPER BOX FOR SUSPENDEDCEILING FIXTURE INSTALL |
RSLV |
08/12/2017 |
08/12/2017 |
11/02/2018 |
| |
| 039 |
(999) |
OTHER (FLOOR: 013) CONTRACTOR AND BUILDING REP NEEDS TO SUPPLY APPLICATIONFOR ALL WORK DONE ON THE 13TH FLOOR AMENITIES SPACE NOT FILED FOR(PANEL UPPER RIGHT AND FEEDER, KITCHEN AREA AND EQUIPMENT (COUNTEROUTLETS NEED GFCI PROTECTED, AND GYM EQUIPMENT QUADS NO DIVIDER FORLINE VOLTAGE AND LOW VOLTAGE WIRING) |
RSLV |
08/12/2017 |
08/12/2017 |
11/02/2018 |
| |
| 040 |
(999) |
OTHER (FLOOR: 013)110.2 BREAKERS IN PP13 NOT CORRECT TYPE NOT INSTALLED CORRECTLY |
RSLV |
08/12/2017 |
08/12/2017 |
11/02/2018 |
| |
| 041 |
(293) |
GFCI NOT PROVIDED FOR JACUZZI (FLOOR: 017)680.71 JACUZZI NOT PROVIDED WITH GFCI, NEED TO CHECK BONDING OF TUBIN BATHROOM |
RSLV |
08/12/2017 |
08/12/2017 |
07/02/2019 |
| |
| 042 |
(999) |
OTHER (FLOOR: 018) 110.3 DAMAGED PANEL IN UNIT ON 18TH FLOOR |
RSLV |
08/12/2017 |
08/12/2017 |
07/02/2019 |
| |
| 043 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (FLOOR: 019)210.8 GFCI NOT PROVIDED FOR OUTLETS WITHIN 6FT FEET OF SINK INKITCHENS FROM ROOF TO 2 FLOOR (EITHER IN FLOOR OR WALL ) |
RSLV |
08/12/2017 |
08/12/2017 |
07/02/2019 |
| |
| 044 |
(999) |
OTHER (CELLAR)NEED CURRENT APPROVED DRAWINGS FOR NEXT INSPECTION FOR ADVISORYPORTION, ALSO THE CONTRACTOR NEEDS TO AMEND THE APP FOR ALL MISSINGRISERS AND FEEDERS FOR ALL PANELS AND SERVICE SWITCHES, ALSO MUSTADD IN ALL SERVICE SWITCHES ALL FIRST LEVEL |
RSLV |
08/12/2017 |
08/12/2017 |
07/02/2019 |
| |
| 045 |
(128) |
NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH (ROOF)250.24 ROOF MECHANICAL ROOM FOR LOWER LEVEL FOUR CKT PANEL NEUTRALBONDED |
RSLV |
08/12/2017 |
08/12/2017 |
11/02/2018 |
| |
| 046 |
( 19) |
DEFECTIVE WIRING IS IN USE (ROOF)110.2 ROOF FANS KEF 1, AND TEF 1 WIRING IS NOT APPROVED METHOD FROMTIME CLOCK TO CONTROLLER BROKEN KO FOR TERMINATION OF SEALTIGHT |
RSLV |
08/12/2017 |
08/12/2017 |
03/15/2018 |
| |
| 047 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (ROOF)210.8 LINE VOLTAGE OUTDOOR DECK LIGHTS MUST BE GFCI PROTECTED ALLAREAS FROM ROOF TO GROUND LEVEL ALL DECKS AND PATIOS |
RSLV |
08/12/2017 |
08/12/2017 |
07/02/2019 |
| |
| 048 |
(999) |
OTHER (ROOF)CONTRACTOR NEEDS TO AMEND THE APP FOR ALL EQUIPMENT ON ROOF HVAC ANDFANS AND LIST ALL DISCONNECTS ON APP |
RSLV |
08/12/2017 |
08/12/2017 |
07/02/2019 |
| |
| 049 |
(999) |
OTHER (ROOF)406.8(B) ALL OUTDOOR OUTLETS MUST BE GFCI, TR ,WR TYPE ROOF, DECKSAND ALL OTHER OUTDOOR AREAS |
RSLV |
08/12/2017 |
08/12/2017 |
03/15/2018 |
| |
| 050 |
(999) |
OTHER (ROOF) 110.2 THIS OBJECTION IS FOR THE INSTALALTION OF THE OUTDOORDECK LIGHTS FROM ROOF TO GROUND LEVEL THEY ARE LINE VOLTAGE AND NOTINSTALLED PER MANUFACTURERS INSTRUCTION THEY ARE NOT RECESSED INDECKS CAUSING A TRIPPING HAZZARD BESIDES NOT INSTALLED PROPERLY(NEED CUT SHEEET FOR FIXTURE ON RETURN VISIT) |
RSLV |
08/12/2017 |
08/12/2017 |
07/02/2019 |
| |
| 051 |
(999) |
OTHER (ROOF) 680.44 PACKAGE HOT TUB UNIT MUST HAVE A LINE A SIGHT SPA GFCIPROTECTED DISCONNECT (BETWEEN 5 TO 10FT) THIS HOT TUB HAS TWOCIRCUITS ONE 220 30AMP AND ONE 220 50AMP BOTH MUST BE GFCI PROTECTEDAND LINE OF SITE |
RSLV |
08/12/2017 |
08/12/2017 |
11/02/2018 |
| |
| 052 |
(999) |
OTHER (ROOF)330.12 MC CABLE INSTALLED EXPOSED ON ROOF AND DECK AREAS COMING OUTOF THE WALL AT BASE TOP DUPLEX WIRING COMING FROM UNDER THE WALL BYGFCI OUTLET, AND IN DECK AREAS PROTRUDING FROM UNDER THE WALL PATIODECKS |
RSLV |
08/12/2017 |
08/12/2017 |
07/02/2019 |
| |
| 053 |
(999) |
OTHER (BASEMENT) SERVICE ROOM HDP BREAKER SLOTS OPEN 408.7 |
RSLV |
11/02/2018 |
11/02/2018 |
07/02/2019 |
| |
| 054 |
(999) |
OTHER (BASEMENT) BATHROOM INSTA HOT NO DISCONNECT 422.30 |
RSLV |
11/02/2018 |
11/02/2018 |
07/02/2019 |
| |
| 055 |
(999) |
OTHER (ROOF)LED TRANSFORMER BOX BONDING, COVERS, FIXTURE WIRE 314, 400, 240.4 |
RSLV |
11/02/2018 |
11/02/2018 |
07/02/2019 |
| |
| 056 |
(999) |
OTHER (ROOF) LFMC 6" BOX TO UNDER ROOF DECK 314.29 |
RSLV |
11/02/2018 |
11/02/2018 |
07/02/2019 |
| |
| 057 |
(101) |
CONDUCTORS AND/OR EQUIPMENT USED IS NOT APPROVED (ALL FLOORS)KITCHEN UNDER CABINET LIGHTS TRANSFORMERS NOT LISTED T-OUT |
RSLV |
01/02/2019 |
01/02/2019 |
07/02/2019 |
| |
| 058 |
(169) |
TEMPORARY CONSTRUCTION WIRING IS NOT REMOVED (ALL FLOORS) T-OUT HALLWAYS |
RSLV |
01/02/2019 |
01/02/2019 |
07/02/2019 |
| |
| 059 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX (ALL FLOORS) PANELS T-OUT APTS |
RSLV |
01/02/2019 |
01/02/2019 |
07/02/2019 |
| |
| 060 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY (ALL FLOORS) T-OUT APTS |
RSLV |
01/02/2019 |
01/02/2019 |
07/02/2019 |
| |
| 061 |
(999) |
OTHER (ALL FLOORS)RECEPTACLES SET BACK IN COMBUSTIBLE (WALL PAPER )T-OUT HALLWAYS ANDAPTS |
RSLV |
01/02/2019 |
01/02/2019 |
07/02/2019 |
| |
| 062 |
(101) |
CONDUCTORS AND/OR EQUIPMENT USED IS NOT APPROVED (CELLAR) NEED LISTING FOR 4 /600 MC WIRE (SERVICE AREA ) |
RSLV |
01/02/2019 |
01/02/2019 |
07/02/2019 |
| |
| 063 |
( 19) |
DEFECTIVE WIRING IS IN USE (CELLAR) TWO WATER MAINS IN THE BLDG |
RSLV |
01/02/2019 |
01/02/2019 |
07/02/2019 |
| |
| 064 |
(999) |
OTHER (CELLAR) ARC FLASH WARNING LABELS NOT PROVIDED T-OUT SERVICE AREA |
RSLV |
01/02/2019 |
01/02/2019 |
07/02/2019 |