Electrical Application Details for App #: M368456
Premises: 1162 2 AVENUE MANHATTAN BIN: 1090528     Block: 1436   Lot: 1
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 301 E 61 ST Census Tract:   110
CEL,MEZ,ROOF,1 THRU 19 Admin Area:   M - MANHATTAN Inspection Area:   M
NEW YORK, NY 10065 Community Board:   108
Related Job Number:    121163436
DOB Cross Street(s):    2 AVENUE,    PEDESTRIAN AND BIKE PATH LINK
Status:   C - JOB IS SIGNED OFF 09/26/2019
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   06/08/2015 Job Start Date:   06/02/2015
Last Change:   09/26/2019 Job End Date:   06/09/2017
Appointment Status:   
Last Inspection By:   VAZQUEZ, LOUIS       On     07/02/2019      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012245 Licensee Name: PETER ARANA
Firm: 003988 Firm Name: SANT-TEC ELECTRIC INC
Firm Phone: 718-644-7645  Firm Address: 516 INDUSTRIAL LOOP 2ND FL STATEN ISLAND NY 10309 

Work Started or Filed by Others: YES
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
L - LIGHTING WORK
Total Fee:  $4,110.50
Hurricane Sandy Damage:   No
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  121163436
Building Used As:   Z - Commercial/Residential (30  Stores, 1 Apartments)
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   52355     Submittal #: 14A0065  
Owner / Occup: GORDY CHANCE
Owner Business Name: 61ST & 2ND NYC LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  3  
D. 601 Up to 1200 AMPS  1  
E. Over 1200 AMPS  1  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  16  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  4  
D. Over 250 MCM  10  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  31  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  4  
D. 3 Phase Over 225 AMPS  3  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    20  10    41  20  338         
001    14    34         
MEZ    10    31  16  28         
002    12  124    53  90  30         
003    12  123    52  90  30         
004    12  104    50  95  60  30         
005    10  101    42  87  25         
006    84    40  91  25         
007    90    35  77  25         
008    60    30  78  25         
009    88    33  75  25         
010    60    30  79  20         
011    90    35  75  25         
012    60    30  78  55  25         
013    18    55  20         
014    47    28  60  15         
015    47    22  63  15         
016    65    29  52  20         
017    65    30  49  20         
018    48    31  72  30         
019    45    19  44  20         
ROF    15    24         
Buildings Total 191  1350    610  1440     801           
Total Units : 4392 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 1
Existing Meters 0 + New Meters 2 - Removed Meters 0 = Total Meters 2

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 06/08/2015 Notice: 1 - FIRST NOTICE 01/03/2019
Power Issued: 06/08/2015 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M368456
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/08/2017 05/08/2017 TOR V (30) (7)
INSPECTION COMMENTS: FAIL 18 AND 17 FL INSPECTED ONLY NEED T-OUT INSP.
 
(2) 07/14/2017 07/18/2017 PHG V X (350) (25)
INSPECTION COMMENTS: INSPECTED ADVISORY BOARD AND 11/12 DUPLEX AND 11B ONLY
 
(3) 08/12/2017 08/14/2017 MQY V X (320) (20)
INSPECTION COMMENTS: CONTRACTOR NEEDS TO FIX APP SEE NOTES IN OBJECTIONS, NEED CURRENT APPROVED ADVISORY DRAWINGS FOR NEXT INSPECTION. DID NOT INSPECT ADVISORY, GENERATOR, AND ALL BASEMENT ROOMS NOT TIME NO DRAWINGS LICENSEE NEEDS TO CHECK WIRING TOUT
 
(4) 03/15/2018 03/16/2018 CBK J Y (320) (0)
INSPECTION COMMENTS: INSPECT OBJECTIONS ONLY. OBJECTION PARTIALLY REMOVED.
 
(5) 11/02/2018 11/02/2018 STP V Y (280) (4)
INSPECTION COMMENTS: FAIL. DID NOT HAVE REVISED DRAWINGS FOR ADVISORY BOARD PORTION OF JOB AND WE DID NOT HAVE ACCESS TO ANY APARTMENTS FOR THIS INSPECTION. OBJECTIONS THAT WERE REMOVED WERE COMMON AREA.
 
(6) 01/02/2019 01/03/2019 TOR V Y (415) (8)
INSPECTION COMMENTS: FAIL DRWG NEED TO BE CORRECTED OBJ INSPECTED ONLY
 
(7) 06/08/2019 06/08/2019 CDX N (55) (0) Y
INSPECTION COMMENTS: FAIL. NO SHOW. CALLED CONTRACTOR DOES NOT ANSWERED.
 
(8) 07/02/2019 07/03/2019 LV1 C R (195) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: M368456
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (169) TEMPORARY CONSTRUCTION WIRING IS NOT REMOVED
(FLOOR: 018) T-OUT
RSLV 05/08/2017 05/08/2017 03/15/2018
 
002 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(FLOOR: 018) NOT REFLECTING FIELD CONDITION AS WELL ON 17 FL
RSLV 05/08/2017 05/08/2017 07/02/2019
 
003 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(FLOOR: 018) AS NEEDED 17 FL INCLUDED
RSLV 05/08/2017 05/08/2017 01/02/2019
 
004 (999) OTHER
(FLOOR: 018) MC NOT GROUNDED T-OUT AS WELL 17 FL 250.122 ,250.118
RSLV 05/08/2017 05/08/2017 01/02/2019
 
005 (999) OTHER
(FLOOR: 018) NO HANDLE TIES T-OUT AS WELL 17 FL 210.4B
RSLV 05/08/2017 05/08/2017 03/15/2018
 
006 (999) OTHER
(FLOOR: 018)2 MINIMUM CIRCUITS ON COUNTER NOT PROVIDED KITCHEN AREA AS WELL ON17 FL 210.11
RSLV 05/08/2017 05/08/2017 01/02/2019
 
007 (999) OTHER
(FLOOR: 018)NO WR RECEPTACLE PROVIDED T-OUT AS WELL 17 FL (ALL BALCONY AREA)406.8
RSLV 05/08/2017 05/08/2017 03/15/2018
 
008 (110) SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED
(FLOOR: 013) MDP 13 FL BATHROOM NO WORKING SPACE FOR MDP
RSLV 07/14/2017 07/14/2017 07/02/2019
 
009 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(ALL FLOORS) AIR HANDLERS OVER FUSED T OUT
RSLV 07/14/2017 07/14/2017 03/15/2018
 
010 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
(BASEMENT) NO BOND FOR CON ED BOX LOADS
RSLV 07/14/2017 07/14/2017 07/02/2019
 
011 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
(BASEMENT) NO BONDING IN PIPES ABOVE CT 250.93
RSLV 07/14/2017 07/14/2017 07/02/2019
 
012 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
(BASEMENT) 2 INCH LINE CON ED BOX AND SERVICE SW 250.93
RSLV 07/14/2017 07/14/2017 07/02/2019
 
013 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(BASEMENT) FIRE PUMP UNDER FUSED 695..4
RSLV 07/14/2017 07/14/2017 03/15/2018
 
014 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
(BASEMENT) FIRE PUMP GEC UNDER SIZED 250.122
RSLV 07/14/2017 07/14/2017 07/02/2019
 
015 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(BASEMENT) NO GROUPING IN TROUGH AS PER PRINT
RSLV 07/14/2017 07/14/2017 07/02/2019
 
016 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(BASEMENT) SERVICE SW 4 CONDUCTORS LOAD NOT AS PER PRINT
RSLV 07/14/2017 07/14/2017 07/02/2019
 
017 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(BASEMENT) GENERATOR BREAKER NOT AS PER PRINT
RSLV 07/14/2017 07/14/2017 07/02/2019
 
018 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(BASEMENT) NO PUSH BAR IN SERVICE RM 110.26
RSLV 07/14/2017 07/14/2017 07/02/2019
 
019 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(BASEMENT) SERVICE ENTRACNCE CON ED FEED NOT AS PER PRINT
RSLV 07/14/2017 07/14/2017 07/02/2019
 
020 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(BASEMENT) FUSES DONT MATCH IN SERVICE 2,3 ,4
RSLV 07/14/2017 07/14/2017 07/02/2019
 
021 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(BASEMENT) BREAKERS ADEDED TO MDP RPD2 HDP
RSLV 07/14/2017 07/14/2017 07/02/2019
 
022 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(BASEMENT) FIRE ALARM ATS NO AS PER PRINT
RSLV 07/14/2017 07/14/2017 07/02/2019
 
023 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(BASEMENT) TAPS NOT IN 10 FT AS PER PRINT
RSLV 07/14/2017 07/14/2017 07/02/2019
 
024 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(BASEMENT)200 AMP SERVICE SW GROUNDING NOT AS PER PRINT 250.66 250.53
RSLV 07/14/2017 07/14/2017 07/02/2019
 
025 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
(BASEMENT) NEUTRAL IN GENERATOR NOT BONDED 250.66
RSLV 07/14/2017 07/14/2017 07/02/2019
 
026 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
(BASEMENT)FIRE ALARM FROM GENERATOR NO GEC AND AND BONDING JUMPER 250.8250.66
RSLV 07/14/2017 07/14/2017 07/02/2019
 
027 ( 9) SQ AREA OF SUM OF CONDUCTORS EXCEEDS SQ AREA FILL OF RACEWAY
(BASEMENT) MILL CUT FROM LINE OF GENERATOR
RSLV 07/14/2017 07/14/2017 07/02/2019
 
028 (999) OTHER
(BASEMENT) NO SUPPLEMENT GROUND FRO ALL SERVICE SW 250.53
RSLV 07/14/2017 07/14/2017 01/02/2019
 
029 (999) OTHER
(BASEMENT) BREAKER IN GENERATOR IS BROKEN 110.3
RSLV 07/14/2017 07/14/2017 07/02/2019
 
030 (999) OTHER
(BASEMENT) NETURAL ON LINE SIDE OF LINK 408.60
RSLV 07/14/2017 07/14/2017 03/15/2018
 
031 (999) OTHER
(BASEMENT) SCREWS NOT TIGHT ON ELD LINE BUS BAR 110.3
RSLV 07/14/2017 07/14/2017 01/02/2019
 
032 (999) OTHER
(BASEMENT) JOCKEY PUMP TAP NOT PERMITED
RSLV 07/14/2017 07/14/2017 03/15/2018
 
033 (128) NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH
(FLOOR: 002)250.24 2ND FLOOR MECHANICAL ROOM PANEL NEUTRAL BONDED (ALSO KO SEALSOPEN AND GROUPING MISSING)
RSLV 08/12/2017 08/12/2017 07/02/2019
 
034 ( 18) DEFECTIVE RECEPTACLES ARE IN USE
(FLOOR: 002)110.2 THERE IS DEFECTIVE OUTLETS IN TOP PENT HOUSE NOT WORKING INLIVING ROOM AND KITCHEN AREAS,
RSLV 08/12/2017 08/12/2017 03/15/2018
 
035 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(FLOOR: 002)408.4 ALL PANELS NEED PROPER AND COMPLETE DIRECTORIES FROM ROOF TOCELLAR
RSLV 08/12/2017 08/12/2017 07/02/2019
 
036 ( 53) GFCI HAS NOT BEEN PROVIDED
(FLOOR: 002)210.52D IN ALL BATHROOMS WITH DOUBLE SINKS MUST HAVE A GFCI WITHIN3FT OF THE OUTER EDGE OF THE SINK NEED SECOND SINK OUTLET SO WIRINGWILL NOT CROSS SINK ON RIGHT THIS OBJECTION IS FOR ALL UNITS FROMROOF TO THE BASEMENT
RSLV 08/12/2017 08/12/2017 07/02/2019
 
037 (999) OTHER
(FLOOR: 002) 110.2 TWO GANG FLOOR OUTLETS NO DIVIDER FOR VOLTAGES
RSLV 08/12/2017 08/12/2017 07/02/2019
 
038 ( 15) FLEXIBLE CORDS USED AS PERMANENT WIRING METHOD
(FLOOR: 013)400.8 THREE PENDANT LIGHTS OVER TABLE IN AMENITIES AREA NOTINSTALLED IN A APPROVED MANNER FLEXIBLE WIRING CANNOT BE INSTALLEDIN THE CEILING PLENUM AND BOX MUST BE PROPER BOX FOR SUSPENDEDCEILING FIXTURE INSTALL
RSLV 08/12/2017 08/12/2017 11/02/2018
 
039 (999) OTHER
(FLOOR: 013) CONTRACTOR AND BUILDING REP NEEDS TO SUPPLY APPLICATIONFOR ALL WORK DONE ON THE 13TH FLOOR AMENITIES SPACE NOT FILED FOR(PANEL UPPER RIGHT AND FEEDER, KITCHEN AREA AND EQUIPMENT (COUNTEROUTLETS NEED GFCI PROTECTED, AND GYM EQUIPMENT QUADS NO DIVIDER FORLINE VOLTAGE AND LOW VOLTAGE WIRING)
RSLV 08/12/2017 08/12/2017 11/02/2018
 
040 (999) OTHER
(FLOOR: 013)110.2 BREAKERS IN PP13 NOT CORRECT TYPE NOT INSTALLED CORRECTLY
RSLV 08/12/2017 08/12/2017 11/02/2018
 
041 (293) GFCI NOT PROVIDED FOR JACUZZI
(FLOOR: 017)680.71 JACUZZI NOT PROVIDED WITH GFCI, NEED TO CHECK BONDING OF TUBIN BATHROOM
RSLV 08/12/2017 08/12/2017 07/02/2019
 
042 (999) OTHER
(FLOOR: 018) 110.3 DAMAGED PANEL IN UNIT ON 18TH FLOOR
RSLV 08/12/2017 08/12/2017 07/02/2019
 
043 ( 53) GFCI HAS NOT BEEN PROVIDED
(FLOOR: 019)210.8 GFCI NOT PROVIDED FOR OUTLETS WITHIN 6FT FEET OF SINK INKITCHENS FROM ROOF TO 2 FLOOR (EITHER IN FLOOR OR WALL )
RSLV 08/12/2017 08/12/2017 07/02/2019
 
044 (999) OTHER
(CELLAR)NEED CURRENT APPROVED DRAWINGS FOR NEXT INSPECTION FOR ADVISORYPORTION, ALSO THE CONTRACTOR NEEDS TO AMEND THE APP FOR ALL MISSINGRISERS AND FEEDERS FOR ALL PANELS AND SERVICE SWITCHES, ALSO MUSTADD IN ALL SERVICE SWITCHES ALL FIRST LEVEL
RSLV 08/12/2017 08/12/2017 07/02/2019
 
045 (128) NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH
(ROOF)250.24 ROOF MECHANICAL ROOM FOR LOWER LEVEL FOUR CKT PANEL NEUTRALBONDED
RSLV 08/12/2017 08/12/2017 11/02/2018
 
046 ( 19) DEFECTIVE WIRING IS IN USE
(ROOF)110.2 ROOF FANS KEF 1, AND TEF 1 WIRING IS NOT APPROVED METHOD FROMTIME CLOCK TO CONTROLLER BROKEN KO FOR TERMINATION OF SEALTIGHT
RSLV 08/12/2017 08/12/2017 03/15/2018
 
047 ( 53) GFCI HAS NOT BEEN PROVIDED
(ROOF)210.8 LINE VOLTAGE OUTDOOR DECK LIGHTS MUST BE GFCI PROTECTED ALLAREAS FROM ROOF TO GROUND LEVEL ALL DECKS AND PATIOS
RSLV 08/12/2017 08/12/2017 07/02/2019
 
048 (999) OTHER
(ROOF)CONTRACTOR NEEDS TO AMEND THE APP FOR ALL EQUIPMENT ON ROOF HVAC ANDFANS AND LIST ALL DISCONNECTS ON APP
RSLV 08/12/2017 08/12/2017 07/02/2019
 
049 (999) OTHER
(ROOF)406.8(B) ALL OUTDOOR OUTLETS MUST BE GFCI, TR ,WR TYPE ROOF, DECKSAND ALL OTHER OUTDOOR AREAS
RSLV 08/12/2017 08/12/2017 03/15/2018
 
050 (999) OTHER
(ROOF) 110.2 THIS OBJECTION IS FOR THE INSTALALTION OF THE OUTDOORDECK LIGHTS FROM ROOF TO GROUND LEVEL THEY ARE LINE VOLTAGE AND NOTINSTALLED PER MANUFACTURERS INSTRUCTION THEY ARE NOT RECESSED INDECKS CAUSING A TRIPPING HAZZARD BESIDES NOT INSTALLED PROPERLY(NEED CUT SHEEET FOR FIXTURE ON RETURN VISIT)
RSLV 08/12/2017 08/12/2017 07/02/2019
 
051 (999) OTHER
(ROOF) 680.44 PACKAGE HOT TUB UNIT MUST HAVE A LINE A SIGHT SPA GFCIPROTECTED DISCONNECT (BETWEEN 5 TO 10FT) THIS HOT TUB HAS TWOCIRCUITS ONE 220 30AMP AND ONE 220 50AMP BOTH MUST BE GFCI PROTECTEDAND LINE OF SITE
RSLV 08/12/2017 08/12/2017 11/02/2018
 
052 (999) OTHER
(ROOF)330.12 MC CABLE INSTALLED EXPOSED ON ROOF AND DECK AREAS COMING OUTOF THE WALL AT BASE TOP DUPLEX WIRING COMING FROM UNDER THE WALL BYGFCI OUTLET, AND IN DECK AREAS PROTRUDING FROM UNDER THE WALL PATIODECKS
RSLV 08/12/2017 08/12/2017 07/02/2019
 
053 (999) OTHER
(BASEMENT) SERVICE ROOM HDP BREAKER SLOTS OPEN 408.7
RSLV 11/02/2018 11/02/2018 07/02/2019
 
054 (999) OTHER
(BASEMENT) BATHROOM INSTA HOT NO DISCONNECT 422.30
RSLV 11/02/2018 11/02/2018 07/02/2019
 
055 (999) OTHER
(ROOF)LED TRANSFORMER BOX BONDING, COVERS, FIXTURE WIRE 314, 400, 240.4
RSLV 11/02/2018 11/02/2018 07/02/2019
 
056 (999) OTHER
(ROOF) LFMC 6" BOX TO UNDER ROOF DECK 314.29
RSLV 11/02/2018 11/02/2018 07/02/2019
 
057 (101) CONDUCTORS AND/OR EQUIPMENT USED IS NOT APPROVED
(ALL FLOORS)KITCHEN UNDER CABINET LIGHTS TRANSFORMERS NOT LISTED T-OUT
RSLV 01/02/2019 01/02/2019 07/02/2019
 
058 (169) TEMPORARY CONSTRUCTION WIRING IS NOT REMOVED
(ALL FLOORS) T-OUT HALLWAYS
RSLV 01/02/2019 01/02/2019 07/02/2019
 
059 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
(ALL FLOORS) PANELS T-OUT APTS
RSLV 01/02/2019 01/02/2019 07/02/2019
 
060 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(ALL FLOORS) T-OUT APTS
RSLV 01/02/2019 01/02/2019 07/02/2019
 
061 (999) OTHER
(ALL FLOORS)RECEPTACLES SET BACK IN COMBUSTIBLE (WALL PAPER )T-OUT HALLWAYS ANDAPTS
RSLV 01/02/2019 01/02/2019 07/02/2019
 
062 (101) CONDUCTORS AND/OR EQUIPMENT USED IS NOT APPROVED
(CELLAR) NEED LISTING FOR 4 /600 MC WIRE (SERVICE AREA )
RSLV 01/02/2019 01/02/2019 07/02/2019
 
063 ( 19) DEFECTIVE WIRING IS IN USE
(CELLAR) TWO WATER MAINS IN THE BLDG
RSLV 01/02/2019 01/02/2019 07/02/2019
 
064 (999) OTHER
(CELLAR) ARC FLASH WARNING LABELS NOT PROVIDED T-OUT SERVICE AREA
RSLV 01/02/2019 01/02/2019 07/02/2019