BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M368444
Premises: 109 NASSAU STREET MANHATTAN BIN: 1089790     Block: 90   Lot: 17
   
Application Completed and Certified

Filed: 113 NASSAU ST Census Tract:   15.01
4TH & 5TH FLOORS Admin Area:   M - MANHATTAN Inspection Area:   W
NEW YORK, NY 10038 Community Board:   101
Special Place Name:   ILSC LEARNING CENTER
DOB Cross Street(s):   ANN STREET,    BEEKMAN STREET
Status:   C - JOB IS SIGNED OFF 09/01/2015
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   06/08/2015 Job Start Date:   06/01/2015
Last Change:   09/01/2015 Job End Date:   05/30/2016
Appointment Status:   
Last Inspection By:   BERGMAN EDUARD       On     08/27/2015      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011535 Licensee Name: JEFFREY M LIU
Firm: 004269 Firm Name: UNITED ELEC & LIGHTING CO
Firm Phone: 718-740-2200  Firm Address: 200-24 HOLLIS AVENUE CORP SAINT ALBANS NY 11412 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $523.75
Hurricane Sandy Damage:   No
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   K - Store
Store / Other:   LEARNING CENTER
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval #:   53031     Submittal #: 15A0328  
Owner / Occup: DAVID HUGHES
Owner Business Name: ILSC LEARNING CENTER
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  
C. 201 Up to 600 AMPS  1  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  
D. Over 250 MCM  1  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  3  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
004      105    18  121             
005      35    37             
Buildings Total   140    27  158                
Total Units : 325 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 1
Existing Meters 0 + New Meters 2 - Removed Meters 0 = Total Meters 2

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 06/08/2015 Notice: 1 - FIRST NOTICE 07/21/2015
Power Issued: 06/08/2015 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  APPLICATION WAS PREVIOUSLY FILED UNDER M349978 BUT ADVISORYBOARD APPROVED AFTER THE APPLICATION. THISIS THE REPLACEMENTAPPROVAL #53031-SUBMITTAL #15A0328

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M368444
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/10/2015 07/21/2015 EID A E (120) (4) Y
INSPECTION COMMENTS: NONE
 
(2) 08/27/2015 08/28/2015 EID J Y E (35) (0) Y
INSPECTION COMMENTS: NONE
 
(3) 08/27/2015 09/01/2015 EDB C R E (75) (0) Y
INSPECTION COMMENTS: INSPECT OBJECTION ONLY

OBJECTION FOR APPLICATION #: M368444
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
4&5 FLOOR EXIT SIGNS NOT PROPERLY SUPPORTED (AMD 410.30)
RSLV 07/10/2015 07/10/2015 08/27/2015
 
002 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
4&5 FLOOR 3/4 PIPE IN CEILINGS NOT PROPERLY SUPPORTED T-OUT (358.30
RSLV 07/10/2015 08/27/2015 08/27/2015
 
003 (999) OTHER
4&5 FLOOR REC BOX SET BACK MORE THAN 1/4" (314.20)
RSLV 07/10/2015 07/10/2015 08/27/2015
 
004 (999) OTHER
4&5 FLOOR DRINKING FOUNTAIN NOT PROVIDED WITH GFCI (422.52)
RSLV 07/10/2015 07/10/2015 08/27/2015



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.