BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M368386
Premises: 375 SOUTH END AVENUE MANHATTAN BIN: 1083375     Block: 16   Lot: 100
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 375 S END AV Census Tract:   317.04 Health Area:  8900
BASEMENT Admin Area:   M - MANHATTAN Inspection Area:   R
NEW YORK, NY 10280 Community Board:   101
DOB Cross Street(s):   ALBANY STREET,    NORTH COVE BIKE PATH
Status:   C - JOB IS SIGNED OFF 02/20/2024
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/05/2015 9:49 AM
Application Entered:   06/05/2015 Job Start Date:   06/05/2015
Last Change:   02/20/2024 Job End Date:   06/05/2016
Appointment Status:   
Last Inspection By:   ADAM ADAMSKI       On     01/29/2024      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011246 Licensee Name: LINVAL J BROWN
Firm: 002651 Firm Name: LINPHILL ELEC'L CONTR.
Firm Phone: 718-653-3032  Firm Address: 4850 WHITE PLAINS ROAD..2ND FL BRONX NY 10470 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
9 - OTHER
Total Fee:  $3,865.00
Other Work:   RELOCATING MDP
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   580 APARTMENTS
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: GREGG TUMMING
Owner Business Name: LEFRAK
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  2  2 SETS 3#2
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  6  6 SETS OF 4 3/0
D. Over 250 MCM  45  45 SETS OF 4 600 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  2  4000 42 CKT 3PH 4W PNL
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 01/05/2024
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  RELOCATING ELECTRICAL DISTRIBUTION SERVICE SPECIAL PERMISSION APPROVAL NO 52599 SUBMITTAL NO 14A0577

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M368386
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/15/2023 09/16/2023 ASK V (50) (1)
INSPECTION COMMENTS: FAIL. INSPECTION INCOMPLETE. OBJECTION ISSUED. ATOI LINVAL. FULL INSPETION WITH APROVED A/B DRAWINGS .
 
(2) 01/04/2024 01/05/2024 ASK V R (80) (1)
INSPECTION COMMENTS: FAIL. INSPECTION COMPLETE. OBJECTION ISSUED. ATOI LINVAL
 
(3) 01/29/2024 01/30/2024 ASK C R (77) (0)
INSPECTION COMMENTS: PASS. INSPECTION COMPLETE. ATOI FRANKE

OBJECTION FOR APPLICATION #: M368386
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 4) SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL
(ALL FLOORS)SERVICE OVER 1000KVA NOT SUBMITED FOR APPROVAL ART AM. 110.2
RSLV 09/15/2023 09/15/2023 01/04/2024
 
002 (221) NOT INSTALLED PER ADVISORY BOARD DRAWING
(ALL FLOORS)FUSE TYPE AND SIZE NOT AS PER AB DRAWINGS T-OUT. ART.AM 110.2B
RSLV 01/04/2024 01/04/2024 01/29/2024



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.