BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M368034
Premises: 341 EAST 73 STREET MANHATTAN BIN: 1044904     Block: 1448   Lot: 17
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 345 E 73 ST Census Tract:   126 Health Area:  4200
APT#8H Admin Area:   M - MANHATTAN Inspection Area:   K
NEW YORK, NY 10021 Community Board:   108
DOB Cross Street(s):    2 AVENUE,    1 AVENUE
Status:   C - JOB IS SIGNED OFF 02/08/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/28/2015 2:46 PM
Application Entered:   05/28/2015 Job Start Date:   05/28/2015
Last Change:   02/08/2016 Job End Date:   01/30/2016
Appointment Status:   
Last Inspection By:   FATA, LUIGI       On     02/05/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010891 Licensee Name: DARIO KNESICH
Firm: 004084 Firm Name: GLENDALE ELECTL CONTNG IN
Firm Phone: 718-772-4544  Firm Address: 58-80 56TH STREET MASPETH NY 11378 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
L - LIGHTING WORK
Total Fee:  $72.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   Yes
Job Number:  122346096
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JOSEPH DIAMENTE
Owner Business Name: 345 EAST 73RD OWNERS CORP
Authorized Representative:  JOSEPH DIAMENTE
Relationship To Owner:   UNIT OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
008                       
008  8H  26  30    22               
Buildings Total 26  30    22                  
Total Units : 78 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 12/21/2015
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M368034
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/15/2015 12/21/2015 GYM V (90) (6)
INSPECTION COMMENTS: 4 AC UNITS INSTALLED
 
(2) 02/05/2016 02/08/2016 LUF C R (40) (0)
INSPECTION COMMENTS: PASS

OBJECTION FOR APPLICATION #: M368034
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (191) LINE AND LOW VOLTAGE IN SAME RACEWAY FOR A/C UNITS
(FLOOR: 008) NO DEDICATED 20A CIRCUIT PROVIDED AC UNITS ART 210.
RSLV 12/15/2015 12/15/2015 02/05/2016
 
002 (191) LINE AND LOW VOLTAGE IN SAME RACEWAY FOR A/C UNITS
(FLOOR: 008) NO DEDICATED 20A CIRCUIT PROVIDED AC UNITS ART 210.
RSLV 12/15/2015 12/15/2015 02/05/2016
 
003 ( 37) MOTOR DISCONNECT SWITCH HAS NOT BEEN PROVIDED
(FLOOR: 008) PITCH UNITS
RSLV 12/15/2015 12/15/2015 02/05/2016
 
004 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
(FLOOR: 008) BEDROOMS AND DINING ROOM
RSLV 12/15/2015 12/15/2015 02/05/2016
 
005 (999) OTHER
(FLOOR: 008)KITCHEN PLUG MOLD RECEPTACLES NOT LISTED TAMPER RESISTANT ART.406.11
RSLV 12/15/2015 12/15/2015 02/05/2016
 
006 (999) OTHER
(FLOOR: 008)KITCHEN AND BATH ROOMS BOXES SET BACK TOO DEEPLY NOT EXTENDER ART.314.20
RSLV 12/15/2015 12/15/2015 02/05/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back