| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
1 |
125 A |
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(311) |
FIXTURE NOT APPROVED FOR DAMP/WET LOCATION (FLOOR: 015) OVER THE TUB |
RSLV |
02/23/2016 |
02/23/2016 |
05/16/2016 |
| |
| 002 |
( 37) |
MOTOR DISCONNECT SWITCH HAS NOT BEEN PROVIDED (FLOOR: 015) A/C UNIT IN THE ROOM. |
RSLV |
02/23/2016 |
02/23/2016 |
05/16/2016 |
| |
| 003 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED (FLOOR: 015) NOT ALL NEW 110 V AFCI PROTECTED |
RSLV |
02/23/2016 |
02/23/2016 |
06/14/2016 |
| |
| 004 |
( 63) |
RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER (FLOOR: 015) BATHROOM NO GFCI FOR THE SINK |
RSLV |
02/23/2016 |
02/23/2016 |
05/16/2016 |
| |
| 005 |
(109) |
SUFFICIENT WORK SPACE IS NOT PROVIDED/MAINTAINED (FLOOR: 016) NO WORKING SPACE IN FRONT OF PANEL |
RSLV |
02/23/2016 |
02/23/2016 |
05/16/2016 |
| |
| 006 |
( 53) |
GFCI HAS NOT BEEN PROVIDED (FLOOR: 016) NO WTR GDCI FOR OUTDOOR |
RSLV |
02/23/2016 |
02/23/2016 |
05/16/2016 |
| |
| 007 |
(999) |
OTHER (FLOOR: 016) LED DRIVER IS NOT ACCESSIBLE "BURIED" |
RSLV |
05/16/2016 |
05/16/2016 |
06/14/2016 |
| |
| 008 |
(999) |
OTHER (FLOOR: 016) NO DIRECTORY PROVIDED FOR NEW PANEL |
RSLV |
05/16/2016 |
05/16/2016 |
06/14/2016 |