BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: M367689
Premises: 328 SPRING STREET MANHATTAN BIN: 1087495     Block: 595   Lot: 7504
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 330 SPRING ST Census Tract:   37 Health Area:  6800
BASEMEN, RISER AND ROOF Admin Area:   M - MANHATTAN Inspection Area:   U
NEW YORK, NY 10013 Community Board:   102
DOB Cross Street(s):   GREENWICH STREET,    WASHINGTON STREET
Status:   C - JOB IS SIGNED OFF 08/26/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/19/2015 10:06 PM
Application Entered:   05/19/2015 Job Start Date:   05/25/2015
Last Change:   08/26/2016 Job End Date:   09/15/2015
Appointment Status:   
Last Inspection By:   RACEWICZ, TOMASZ       On     08/26/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 012520 Licensee Name: RICHARD E CHIAPPA
Firm: 004443 Firm Name: RC3 ELECTRIC, LLC
Firm Phone: 718-881-8070  Firm Address: 4465 BRONX BLVD BRONX NY 10470 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $192.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Other
Store / Other:   CELL SITE
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: SCOTT PINKHAM
Owner Business Name: VERIZON WIRELESS
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  2  45
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  $50
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS                       
ROF        50         
Buildings Total        50           
Total Units : 59 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 03/01/2016
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  200 AMP FEEDERS, RISER, AND EQUIPMENT WIRING ON ROOF INCLUDING 50 KW GEN

 
Inspection Details
 

INSPECTION FOR APPLICATION #: M367689
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/10/2016 03/01/2016 GYM V (85) (3)
INSPECTION COMMENTS: VERIZON WIRELESS.
 
(2) 05/31/2016 05/31/2016 TOR N (25) (0) Y
INSPECTION COMMENTS: CALLED CONTRACTOR .NO SHOW.
 
(3) 08/26/2016 08/26/2016 TOR C R (45) (0)
INSPECTION COMMENTS: OBJECTIONS ONLY

OBJECTION FOR APPLICATION #: M367689
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 29) OUTLET BOXES ARE NOT COVERED
(BASEMENT) TROUGH.
RSLV 02/10/2016 02/10/2016 08/26/2016
 
002 (999) OTHER
(BASEMENT) CONDUIT NO FIRE STOP PROVIDED ART.
RSLV 02/10/2016 02/10/2016 08/26/2016
 
003 (999) OTHER
(ROOF)VERTICAL CONDUCTORS ARE NOT SUPPORTED TAB. 300.19 (BSMT/ ROOF)
RSLV 02/10/2016 02/10/2016 08/26/2016



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Electrical Inspection Work Order  |  Back