| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
1 |
1-100A |
| B. 101 Up to 200 AMPS |
1 |
1-200A |
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
2 |
2-800A |
| E. Over 1200 AMPS |
1 |
1-1200A |
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
8 |
8-4/0 |
| D. Over 250 MCM |
4 |
4-500MCM |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
8 |
42CIR |
| D. 3 Phase Over 225 AMPS |
8 |
42CIR |
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
2 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (ALL FLOORS)EL.RM: F.P.SERVICE TAP NOT LINE SIDE IN CT CAB.. AMD 110.2(B) |
RSLV |
07/27/2015 |
10/01/2015 |
02/29/2016 |
| |
| 002 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (ALL FLOORS)EL.RM: CON ED/SECTION 5 DETAIL NOT 1/4" X 6" AS PER DRAWINGAMD 110.2(B) |
RSLV |
07/27/2015 |
10/01/2015 |
02/29/2016 |
| |
| 003 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (ALL FLOORS)EL.RM: SERVICE ROOM LAYOUT NOT CONSISTENT WITH DRAWING.. AMD 110.2(B |
RSLV |
07/27/2015 |
10/01/2015 |
02/29/2016 |
| |
| 004 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (ALL FLOORS)EL.RM: CONDUCTORS(SER) FEEDING TIME WARNER AND RETAIL SOT SIZED ASPER DRAWING.. AMD 10.2(B) |
RSLV |
07/27/2015 |
10/01/2015 |
02/29/2016 |
| |
| 005 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER (ALL FLOORS)BSMT: SER RACEWAY FROM SEB TO TROUGH NOT BND TO ENCL.. 250.92(A) |
RSLV |
07/27/2015 |
10/01/2015 |
02/29/2016 |
| |
| 006 |
(129) |
SERVICE SWITCH NEUTRAL NOT BONDED TO ENCLOSURE (ALL FLOORS) EL.RM: ALL SER SWS NEUTRAL NOT BND.. 250.28 |
RSLV |
07/27/2015 |
10/01/2015 |
02/29/2016 |
| |
| 007 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY (ALL FLOORS)EL.RM: ALL SER SWS NO GEC FROM WATER OR SUPPLEMENTRY.. 250.24 |
RSLV |
07/27/2015 |
10/01/2015 |
02/29/2016 |
| |
| 008 |
(136) |
GROUNDING ELECTRODE CONDUCTOR IS NOT CONTINUOUS (ALL FLOORS)EL.RM: GEC CONDUCTOR NOT PROPERLY TERMINATED/NOT CONTINUOUS.. 250.64 |
RSLV |
07/27/2015 |
10/01/2015 |
02/29/2016 |
| |
| 009 |
(999) |
OTHER (ALL FLOORS)BSMT: 3 DISC FOR MTRS EGC DBL UP UNDER SINGLE LUG.. 110.14(A) |
RSLV |
07/27/2015 |
10/01/2015 |
02/29/2016 |
| |
| 010 |
(129) |
SERVICE SWITCH NEUTRAL NOT BONDED TO ENCLOSURE (ALL FLOORS) EL.RM: F.A SER SW NEUTRAL NOT BND.. 250.28 |
RSLV |
07/27/2015 |
10/01/2015 |
02/29/2016 |
| |
| 011 |
(221) |
NOT INSTALLED PER ADVISORY BOARD DRAWING (ALL FLOORS) EL.RM: F.A.ATS LOCATED IN EL.SER.RM.. AMD 110.2.(B) |
RSLV |
07/27/2015 |
10/01/2015 |
02/29/2016 |
| |
| 012 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY (ALL FLOORS) ROOF: CKT BRK PNL NOT LABELLED.. 408.4 |
RSLV |
07/27/2015 |
10/01/2015 |
02/29/2016 |
| |
| 013 |
(999) |
OTHER (ALL FLOORS)EL.RM: F.A. ATS NEUTRAL DBL UP UNDER SINGLE LUG.. 110.14(A) |
RSLV |
07/27/2015 |
10/01/2015 |
02/29/2016 |
| |
| 014 |
(999) |
OTHER ROOF: EXHAUST FANS NO MEANS OF DISC PROVIDED.. 422 |
RSLV |
07/27/2015 |
07/27/2015 |
10/01/2015 |
| |
| 015 |
(129) |
SERVICE SWITCH NEUTRAL NOT BONDED TO ENCLOSURE ROOF: NEUTRAL NOT BND.. 250.2B |
RSLV |
07/27/2015 |
07/27/2015 |
10/01/2015 |
| |
| 016 |
(127) |
NO GROUND HAS BEEN PROVIDED FOR SEPARATELY DERIVED SYSTEM ROOF: GEN NO GEC PROVIDED TO WATER OR STEEL.. 250.20 |
RSLV |
07/27/2015 |
07/27/2015 |
10/01/2015 |
| |
| 017 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER ROOF: GEN RACEWAY AND ENCL NOTBND.. 250.92(A) |
RSLV |
07/27/2015 |
07/27/2015 |
10/01/2015 |
| |
| 018 |
(999) |
OTHER (ALL FLOORS)ROOF: EQUIPMENT GROUND UNDERSIZED ON ALL EXHAUST FANS.. 250.122 |
RSLV |
10/01/2015 |
10/01/2015 |
02/29/2016 |
| |
| 019 |
(999) |
OTHER (ALL FLOORS)12TH FLOOR: HANDLE TIES NEEDED ON 12TH FLOOR PANEL.. 210.4 |
RSLV |
10/01/2015 |
10/01/2015 |
02/29/2016 |
| |
| 020 |
(999) |
OTHER (ALL FLOORS) 12TH FLOOR: BOXES UNCOVERED ON 12 FLOOR |
RSLV |
10/01/2015 |
10/01/2015 |
02/29/2016 |
| |
| 021 |
(999) |
OTHER (ALL FLOORS) ALL FLS: NEED APPROVED FLOOR BOXES.. 314.27C |
RSLV |
10/01/2015 |
10/01/2015 |
02/29/2016 |
| |
| 022 |
(999) |
OTHER (ALL FLOORS) ALL FLS: A.F.C.I.BREAKER MISSING THROUGH-OUT.. 210.12 |
RSLV |
10/01/2015 |
10/01/2015 |
03/18/2016 |
| |
| 023 |
(999) |
OTHER (ALL FLOORS) ALL FLS: OUTLETS MISSING.. 314.25 |
RSLV |
10/01/2015 |
10/01/2015 |
02/29/2016 |
| |
| 024 |
(999) |
OTHER (ALL FLOORS)ALL FLS: FLOOR RECEPTACLES NEED TO BE OF TR TYPE.. 406.11 |
RSLV |
10/01/2015 |
10/01/2015 |
02/29/2016 |
| |
| 025 |
(999) |
OTHER (ALL FLOORS)9TH FL: RECEPTACLES MISSING IN COUNTER TOP & ISLAND.. 314.25 |
RSLV |
10/01/2015 |
10/01/2015 |
02/29/2016 |
| |
| 026 |
(999) |
OTHER (ALL FLOORS) ALL FLS: AC UNITS OVERFUSED THROUGH-OUT.. 240.3 |
RSLV |
10/01/2015 |
10/01/2015 |
03/18/2016 |
| |
| 027 |
(999) |
OTHER (ALL FLOORS) ALL FLS: PANELS REQUIRE DIRECTORIES.. 408.4 |
RSLV |
10/01/2015 |
10/01/2015 |
02/29/2016 |
| |
| 028 |
(999) |
OTHER (ALL FLOORS)12TH FLOOR: RECEPTACLE SET BACK 1/4" WITHOUT PROTECTION.. 314.20 |
RSLV |
10/01/2015 |
10/01/2015 |
03/18/2016 |
| |
| 029 |
(999) |
OTHER (ALL FLOORS)ALL FLS: UNDERSIZED EQUIPMENT GROUND ON DRYERS.. 250.122 |
RSLV |
10/01/2015 |
10/01/2015 |
03/18/2016 |
| |
| 030 |
(999) |
OTHER (ALL FLOORS)THROUGH-OUT: ONLY ONE RECEPTACLE SERVING KITCHEN WITH SINK210.52C4 |
RSLV |
10/01/2015 |
10/01/2015 |
02/29/2016 |
| |
| 031 |
(999) |
OTHER (FLOOR: 001)ALL FLOORS. 30 AMP RATED DRYER PLUG AND RECEPTACLE PROTECTED BY 40AMP CIRCUIT BREAKER. NEC 210.20B |
RSLV |
02/29/2016 |
02/29/2016 |
03/18/2016 |
| |
| 032 |
(999) |
OTHER (FLOOR: 001)MORE THAN 6 FT OF LFMC USED ON LOAD SIDE OF TRASH COMPACTORDISCONNECT SWITCH . AMEND 350.12 |
RSLV |
02/29/2016 |
02/29/2016 |
03/18/2016 |
| |
| 033 |
(999) |
OTHER (BASEMENT) NO PANIC BARS PROVIDED FOR SERVICE ROOM DOOR. NEC 110.26 |
RSLV |
02/29/2016 |
02/29/2016 |
03/18/2016 |
| |
| 034 |
(999) |
OTHER (FLOOR: 009) JUNCTION BOXES NOT ACCESSIBLE ART 314.29 |
RSLV |
03/18/2016 |
03/18/2016 |
04/07/2016 |
| |
| 035 |
(999) |
OTHER (ROOF) GENERATOR NEUTRAL BOND REQUIRED ART 250.28 |
RSLV |
03/18/2016 |
03/18/2016 |
04/07/2016 |